June 2013

If the amplifier box is installed in an area with over pressure or negative pressure in relation to the atmospheric pressure in the tank, the breather tube must be directed to an area with atmospheric pressure equalling the pressure inside the tank. This applies to gauge transmitters only. For absolute transmitters this has no affect, due to the reference to absolute vacuum and not atmospheric pressure. This is also the reason why no breather tube is necessary.

Be sure that the cable glands are tight. Use a torque of 6 Nm.

Shield bracket

Do not fasten to tight

Transducer cable

Breather tube

1/8” NPT fitting for breather tube

Terminal block for Pt100

Breather hose

4-20 mA signal cable

element

 

 

Page 18 of 28

Page 18
Image 18
Emerson MAS 2600 user manual June