Installation & User Manual

June 2013

Ed 19UK

 

 

Absolute Transmitter:

The MAS2600 Absolute Transmitter is available in two ranges.

The output signals are calibrated as follows:

Transducer type

 

: 0.8 - 3.5 bar abs

4

Transducer type

7

: 0.8 - 2.0 bar abs

Selecting the Measuring Range:

When selecting the measuring range it is important to consider the tank height, vent pipe height, the tank type and the specific gravity (SG) of the tank contents.

The transducer measures the height of the fluid (water gauge) from the transducer diaphragm to the surface of the fluid, including the fluid in the vent pipe.

MAS 2600 Amplifier box

4-20 mA TWO WIRE TRANSMITTER

EE

CT5

S/N:

Vent pipe height

 

Tankheight

 

Sensor pos. above

Flange mounted

lowest point

G022P013

 

To ensure measuring accuracy a transducer type within the range no. 4, 5, 6, 7 and 8 is recommended.

Guidelines for selection of transducer measuring ranges are set out in the following.

Selecting the Transducer Type:

Gauge and High Temperature Gauge Transducers:

The Gauge Transmitter is normally used on dry and pressure neutral locations. The Gauge Transmitter is available in 4 ranges:

0-3.5 mH2O.

0-7.0 mH2O.

0-16.0 mH2O.

0-35.0 mH2O.

Page 7 of 28

Page 7
Image 7
Emerson MAS 2600 Selecting the Measuring Range, Selecting the Transducer Type, Transducer type 3.5 bar abs 2.0 bar abs