Reference Manual
IP2013, Rev BA
February 2012
Mobrey MSP422
Mounting the Transmitter Above the Liquid Surface
A
NOTE:
The Mobrey MSP422 is designed to be mounted in a
To help installation, flange accessories and bracket kits are available from Mobrey.
Procedure:
1.Ensure that the transmitter is perpendicular to the liquid surface to maximize the return echo size.
2.Check that the maximum liquid level will not enter the
3.When installing in a tank with a nozzle or
a)Use PTFE tape on the screw thread (Figure
b)Lower transmitter into the tank through the process connection.
c)Turn the transmitter until it is properly secured in the process connection (Figure
d)Tighten to a torque of 1.5 lbf.ft (2 Nm) using the hexagon. Do not use the transmitter housing to tighten.
NOTE:
If the transmitter face does not protrude into the vessel, note the dimensions in Table
4.When installing using a bracket kit (Figure
a)Attach bracket to the disc using the 3 screws provided.
b)Attach bracket and disc to a support. The combined weight of bracket and disc is 16 oz (0,5 kg). For transmitter weight, see "Specifications" on page
c)Use PTFE tape on the screw thread of the transmitter (Figure
d)Insert the transmitter into the disc.
e)Tighten to a torque of 1.5 lbf.ft (2 Nm) using the hexagon. Do not use the transmitter housing to tighten.
NOTE:
The bracket kit contains a stainless steel angle bracket and PVC threaded disc, which may be used to mount the transmitter on a support over the liquid surface. The bracket and disc dimensions are in Figure