Mobrey MSP422

First Measurements

With the transmitter installed and display units selected, the display will show

 

what the instrument calculates as the liquid depth (level). This value is

 

calculated by the microprocessor as being the difference between the

 

distance-to-target being measured and the default value for the datum or

 

bottom reference (b.rEF).

Figure 4-2. Bottom Reference

 

 

 

 

 

 

 

Distance-to-target

Bottom Reference

Depth (Level)

Before changing any of the default values, press the blue button to change the PV display to indicate distance-to-target, as measured by the transmitter from the transmitter face. This value is shown alternately with the text “diSt” to indicate the display is in distance mode. The calculation can be checked against a manual measurement if required.

NOTE:

A useful feature at this stage is that the transmitter can be used as an electronic tape measure. With an empty tank or vessel, the transmitter will read the distance to the bottom of the tank. This distance can be noted and later used when setting b.rEF.

Press the blue button again to get to the echo size. This is a scale of 0 to

100.(It is possible to record a value greater than 100). With the display in this mode, the central “:” cursor will flash once for every echo received, which under normal circumstances will be once per second.

NOTE:

It is useful at this point to check that the maximum echo size available is being received. Adjust the position of the instrument until the highest echo size is continually shown. In most applications, the signal strength will vary over a wide range: 20 to 80.

Press the blue button again to return to the original level reading and start the calibration routine.

NOTE:

The output of the transmitter will vary during programming, as the various default values are changed. The display will automatically revert to the level or distance reading from any other display after a period of four minutes.

4-5