Emerson MA N-00 05-00, UT-P+-STXXXX user manual Sensor Separation

Models: MA N-00 05-00 UT-P+-STXXXX

1 44
Download 44 pages 2.25 Kb
Page 15
Image 15
Sensor Separation

non-hazardous area. Conform to local wiring codes.

When pouring a seal, use a fibre dam to assure proper formation of the seal. Seals should never be poured at temperatures below freezing.

The jacket and shielding of the cable should be stripped back to permit the seal to form around the individual wires. This will prevent air, gas and water leakage through the inside of the shield and into the enclosure.

It is recommended that explosion-proof drains and conduit breathers be used. In some applications, alternate changes in temperature and barometric pressure can cause 'breathing' which allows moist air to enter and circulate inside the conduit. Joints in the conduit system are seldom tight enough to prevent this 'breathing'.

Refer to applicable wiring codes when installing and wiring. After the field wiring has been carefully connected, check that the correct wires are connected to the corresponding terminals and that voltage levels do not exceed the specifications. When the wiring and voltages have been verified remove power

Figure 6 Display Board Layout

from the system. Set the Display board back in place and tighten the two retaining screws.

Sensor Separation

The ST1200, ST1300, ST1400, ST1500 and ST1600 sensors can be installed and wired directly to the UNI- TRAN Premium Plus housing and terminal board as per the wiring diagrams (see Figure 7and 9 ) or they may be remotely mounted using a sensor separation kit (JB2-2-ASSY) which is composed of a junction box and terminal strip (see Figure 8 and 10). The sensor and kit are then connected to the UNI-TRAN Premium Plus.

When sensor separation is required for units using the ST1200, ST1300, ST1400, ST1500 and ST1600 sensor use a minimum of 18AWG shielded copper instrument wire for separations up to 500 feet. Consult factory if greater separations are required (see Appendix B Wire Resistance in Ohms).

NOTE:

Use a minimum of 18AWG shielded copper instrument wire for separations up to 500 feet and 16AWG for separations up to 2000 feet. Consult factory if greater separations are required.

9

Page 15
Image 15
Emerson MA N-00 05-00, UT-P+-STXXXX user manual Sensor Separation