•Low Oil Pressure Safety Changeover = This is the length of time in which the normal Low (Run) Oil Pressure
•High Filter Differential Pressure Safety Changeover = This timer bypasses the High Filter Differential Run Pressure safety settings when the compressor starts. It defines how long the High Filter Differential Start Pressure
•Low Oil Separator Level Safety Changeover Timer = This timer bypasses the low oil level switch for momen- tary drops in the oil level. This timer activates when the low oil level switch opens, and deactivates when the switch closes. If the switch is still open after the timer has timed out, the compressor will be shut down and a trip message will be displayed. This timer is available if the unit is equipped with a low oil separator float switch (the oil level switch is standard on all liquid injection units and optional on all others).
•Low Oil Separator Temperature Safety Changeover = This timer allows Low Oil Separator Start Temperature safety
•Low Oil Injection Temperature Safety Changeover = This timer bypasses the Low Oil Injection Temperature Safety
•Max Restart After Power Failure = This timer forces the compressor to wait for the set time period after a power failure before it can be started automatically. By staggering the time settings of this timer between other compressor panels, the compressors can be allowed to start automatically, one at a time, after a power failure. This will prevent excessive load demand on the power system that could occur if all of the compressor equipment were to start at the same time. The
•Hot Starts/Hr Counter = This counter counts compressor starts. After every start, a