Analog Inputs

BOARD

I/O

DESCRIPTION

TYPE

#

 

 

 

6

1

Motor Current

4-20 mA, 0-5A

6

2

Suction Pressure

0-5V, 1-5 V, 0-10V, 4-20 mA

6

3

Discharge Pressure

0-5V, 1-5 V, 0-10V, 4-20 mA

6

4

Oil Filter Pressure

0-5V, 1-5 V, 0-10V, 4-20 mA

6

5

Oil Manifold Pressure

0-5V, 1-5 V, 0-10V, 4-20 mA

6

6

VRS Oil Injection Pressure

0-5V, 1-5 V, 0-10V, 4-20 mA

6

7

% slide Valve Position

0-5V, 4-20 mA, Potentiometer

6

8

% Volume Position

0-5V, 4-20 mA, Potentiometer

7

9

Suction Temperature

4-20 mA, RTD, ICTD

7

10

Discharge Temperature

4-20 mA, RTD, ICTD

7

11

Oil Separator Temperature

4-20 mA, RTD, ICTD

7

12

Oil Manifold Temperature

4-20 mA, RTD, ICTD

7

13

Process Temperature

4-20 mA, RTD, ICTD

7

14

Level Probe (Cool Compression)

4-20 mA

7

15

Condenser Pressure

0-5V, 1-5 V, 0-10V, 4-20 mA

7

16

Remote Set point

0-5V, 4-20 mA

8

17

Economizer Pressure

0-5V, 1-5 V, 0-10V, 4-20 mA

8

18

Chiller In Temperature

4-20 mA, RTD, ICTD

8

19

Motor Winding Temperature #1

4-20 mA, RTD

8

20

Motor Winding Temperature #2

4-20 mA, RTD

8

21

Motor Winding Temperature #3

4-20 mA, RTD

8

22

Auxiliary #1

0-5V, 1-5V, 0-10V, 4-20 mA, RTD, ICTD

8

23

Auxiliary #2

0-5V, 1-5V, 0-10V, 4-20 mA, RTD, ICTD

8

24

Auxiliary #3

0-5V, 1-5V, 0-10V, 4-20 mA, RTD, ICTD

9

25

Auxiliary #4

0-5V, 1-5V, 0-10V, 4-20 mA, RTD, ICTD

9

26

Auxiliary #5

0-5V, 1-5V, 0-10V, 4-20 mA, RTD, ICTD

9

27

Auxiliary #6

0-5V, 1-5V, 0-10V, 4-20 mA, RTD, ICTD

9

28

Auxiliary #7

0-5V, 1-5V, 0-10V, 4-20 mA, RTD, ICTD

9

29

Bearing Accelerometer/Temp #1

0-5V, 4-20 mA, RTD

9

30

Bearing Accelerometer/Temp #2

0-5V, 4-20 mA, RTD

9

31

Bearing Accelerometer/Temp #3

0-5V, 4-20 mA, RTD

9

32

Bearing Accelerometer/Temp #4

0-5V, 4-20 mA, RTD

 

 

 

 

MOTOR CURRENT – Default is a 0-5 Amp current transformer (CT). Current transformer ratio is set in the calibra- tion screen.

SUCTION PRESSURE – Default signal is 4-20Ma. Suction pressure transducer range and calibration is set in the calibration screen.

DISCHARGE PRESSURE - Default signal is 4-20Ma. Discharge pressure transducer range and calibration is set in the calibration screen.

OIL FILTER PRESSURE - Default signal is 4-20Ma. Oil filter pressure transducer range and calibration is set in the calibration screen.