Analog Outputs

BOARD

I/O #

DESCRIPTION

TYPE

#

 

 

 

10

1

Compressor VFD

4-20 mA

10

2

Condenser VFD

4-20 mA

10

3

% Slide Valve Position

4-20 mA

10

4

Motorized Valve (Cool Compression or Liquid Injection), V+

4-20 mA

10

5

Profile Cooler VFD (Profile only)

4-20 mA

10

6

 

 

10

7

 

 

10

8

 

 

 

 

 

 

COMPRESSOR VFD – 4-20mA output to control compressor motor speed with a Variable Frequency Drive (VFD).

CONDENSER VFD – 4-20mA output to control one condenser fan which is interleaved between the remaining condenser steps for smoother control.

%SLIDE VALVE POSITION – 4-20mA signal that transmits the slide valve position for remote monitoring.

MOTORIZED VALVE (V+) – for a cool compression compressor, this 4-20ma signal controls a motorized valve to regulate the liquid refrigerant level in the oil separator. For a liquid injection application on a standard single screw, this 4-20ma signal controls a motorized valve to regulate the liquid refrigerant injected into the compres- sor for oil cooling purposes.

PROFILE VFD – for a profile unit compressor, this signal controls the aftercooler fan speed which provides oil cool- ing.