Digital Input/Output

BOARD

I/O #

 

DESCRIPTION

 

TYPE

 

 

#

 

 

 

 

 

1

1

 

Compressor Start

 

OUTPUT

1

2

 

Oil Pump Start

 

OUTPUT

1

3

 

Capacity Increase

 

OUTPUT

1

4

 

Capacity Decrease

 

OUTPUT

1

5

 

Volume Increase

 

OUTPUT

1

6

 

Volume Decrease

 

OUTPUT

1

7

 

Oil Sump Heater

 

OUTPUT

1

8

 

Alarm

 

OUTPUT

2

9

 

Slide Valve Set point #1 (Economizer)

 

OUTPUT

2

10

 

Slide Valve Set point #2 (Hot Gas)

 

OUTPUT

2

11

 

Slide Valve Set point #3

 

OUTPUT

2

12

 

Slide Valve Set point #4

 

OUTPUT

2

13

 

Liquid Injection #1

 

OUTPUT

2

14

 

Liquid Injection #2

 

OUTPUT

2

15

 

Remote Enabled

 

OUTPUT

2

16

 

VRS Oil solenoid for old retrofit applications

 

OUTPUT

3

17

 

Comp Motor Starter Auxiliary Contact

 

INPUT

3

18

 

High Level Shutdown

 

INPUT

3

19

 

Oil Level Float Switch #1

 

INPUT

3

20

 

Oil Level Float Switch #2

 

INPUT

3

21

 

Remot Setpoint #1/#2 Selection

 

INPUT

3

22

 

Remote Start/Stop

 

INPUT

3

23

 

Remote Capacity Increase

 

INPUT

3

24

 

Remote Capacity Decrease

 

INPUT

4

25

 

Condenser Step #1

 

OUTPUT

4

26

 

Condenser Step #2

 

OUTPUT

4

27

 

Condenser Step #3

 

OUTPUT

4

28

 

Condenser Step #4

 

OUTPUT

4

29

 

Auxiliary Input #1

 

INPUT

4

30

 

Auxiliary Input #2

 

INPUT

4

31

 

Auxiliary Input #3

 

INPUT

4

32

 

Auxiliary Input #4

 

INPUT

5

33

 

Auxiliary Output #1

 

OUTPUT

5

34

 

Auxiliary Output #2

 

OUTPUT

5

35

 

Auxiliary Output #3

 

OUTPUT

5

36

 

Auxiliary Output #4

 

OUTPUT

5

37

 

Auxiliary Input #5

 

INPUT

5

38

 

Auxiliary Input #6

 

INPUT

5

39

 

Auxiliary Input #7

 

INPUT

5

40

 

Auxiliary Input #8

 

INPUT

 

 

 

 

 

 

COMPRESSOR START OUTPUT – When the Vission 20/20 signals the compressor to start, this output is energized. When the Vission 20/20 signals the compressor to stop, this output is de-energized.

OIL PUMP START OUTPUT - When the Vission 20/20 signals the oil pump to start, this output is energized. When the Vission 20/20 signals the oil pump to stop, this output is de-energized.