Empire Comfort Systems CHG, CHR Leak Testing, Lighting Instructions, GAS Pressure

Models: CHR CHG

1 12
Download 12 pages 55.82 Kb
Page 9
Image 9

LEAK TESTING

WARNING! Before lighting your outdoor gas fireplace be sure to read this section carefully.

Turn gas valve knob to the OFF position. Inspect the gas supply piping or hose prior to turning the gas ON. If there is evidence of cuts, wear, or abrasion, it must be replaced prior to use. The replacement pressure regulators and hose assembly must be the type specified by the manufacturer. Do not use the outdoor gas fireplace if the odor of gas is present.

For LP gas, the pressure regulator and hose assembly supplied with the unit must be used. Install the regulator into the 20 lb. propane cylinder and check the hose and regulator connections for leakage with a soap and water solution before operating your outdoor gas fireplace. Be sure there is gas in the 20 lb. propane cylinder.

1.Before lighting your outdoor gas fireplace, check all connections for leaks using a mild soapy water solution. DO NOT use matches, lighters or flame to check for leaks,

you could cause an explosion. With the outdoor gas fireplace burner control turned OFF, slowly open the cylinder valve by turning the handwheel counterclockwise (right to left). Apply mild soapy water to the connection. If bubbles appear, a leak is indicated. Do not put the product in service! Immediately close the cylinder valve handwheel for propane gas or the manual shutoff valve for natural gas. A qualified service person must be contacted to make the needed repairs.

2.DO NOT SMOKE WHILE LEAK TESTING!

3.For LP gas (propane) models, leak test with a full propane cylinder.

4.For systems other than self-contained LP gas (propane) systems:

A.The outdoor gas fireplace and its individual shut-off valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5kPa).

B.The outdoor gas fireplace must be isolated from the gas supply piping system by closing its own manual shut off valve during any pressure testing of the gas supply piping system at pressures equal to or less than 1/2 psig (3.5kPa).

5.After the installation of all gas-related items: i.e. hose, regulator, LP gas cylinder, natural gas hose or natural gas regulator; the outdoor gas fireplace control valve should be turned OFF and the gas turned ON. This is known as "charging the system." All gas connections must be checked with a soapy solution while the whole system is under pressure.

To make a soap solution, mix together an equal amount of liquid detergent and water.

6.Apply soap mixture to all gas connections. Soap bubbles will appear if there is a leak. Tighten connections to make a proper seal.

If you cannot stop a gas leak turn off the gas supply and call your local gas utility, or the dealer from whom the outdoor gas fireplace was purchased.

Only those parts recommended by the manufacturer should be used on the outdoor gas fireplace. Substitutions will void the warranty. Do not use the outdoor gas fireplace until all connections have been checked and do not leak.

A gas system MUST be tested yearly, or whenever the LP gas cylinder is replaced, or any other gas system part.

WARNING: Locate the gas hose out of pathways where people may trip over it or in areas where the hose may be subject to accidental damage.

When lighting your outdoor gas fireplace always keep your face and body as far away from the burner housing screen as possible.

GAS PRESSURE

Natural Gas

The Natural gas models will have an inlet pressure to the gas valve from a minimum of 7.0" w.c. (1.743kPa) for the purpose of input adjustment to a maximum of 10.5"w.c. (2.615kPa).

Propane Gas

The Propane gas models will have a manifold pressure of approximately 11.0"w.c. (2.739kPa) at the orifice holder with the inlet pressure to the gas valve from a minimum of 11.0"w.c. (2.739kPa) for the purpose of input adjustment to a maximum of 13.0"w.c. (3.237kPa).

A 1/8" (3mm) N.P.T. plugged tapping, accessible for test gauge connection, is located on the orifice holder.

LIGHTING INSTRUCTIONS

1.Push in gas control knob slightly and turn clockwise to "OFF". Note: Knob cannot be turned from "HIGH" to

"OFF" unless knob is pushed in slightly. Do not force.

2.Wait five (5) minutes before attempting to light the burner from a cold start or when a hot outdoor gas fireplace is relit.

3.Turn knob on gas control counterclockwise to "HIGH".

4.Push in control knob all the way and hold in. Immediately light the burner with the piezo ignitor. Continue to hold the control knob in about one (1) minute after the burner is lit. Release knob, and it will pop back up. Burner should remain lit. If it goes out, repeat steps 1 through 4.

If knob does not pop up when released, stop and immediately call your service technician or gas supplier.

If the burner will not stay lit after several tries, turn the gas control knob to OFF and call your service technician or gas supplier.

5.Turn gas control knob counterclockwise from "HIGH" to "MED." or to "LOW".

To Turn Off Gas to Outdoor Gas Fireplace

1.Push in gas control knob slightly and turn clockwise to "OFF". Do not force.

2.Turn off gas supply to outdoor gas fireplace when not in use.

CHG/CHR

Page 9

Page 9
Image 9
Empire Comfort Systems CHG, CHR Lighting Instructions, GAS Pressure, Do not Smoke While Leak Testing