VERTICAL TERMINATION
Determining Minimum Vent Height Above the Roof.
WARNING: Major U.S. building codes specify minimum chimney and/or vent height above the roof top. These minimum heights are necessary in the interest of safety. These specifica- tions are summarized in Figure 9.
ROOF PITCH | H (Min.) |
Flat to 6/12 | 12" (305 mm) |
6/12 to 7/12 | 15" (381 mm) |
Over 7/12 to 8/12 | 18" (457 mm) |
Over 8/12 to 16/12 | 24" (610 mm) |
Over 16/12 to 21/12 | 36" (914 mm) |
Figure 9
Note that for steep roof pitches, the vent height must be increased. In high wind conditions, nearby trees, adjoining roof lines, steep pitched roofs, and other similar factors can result in poor draft, or
Vertical Through the Roof Applications
The Gas Fireplace Insert has been approved for:
a)Vertical installations up to 35 feet in height (top of insert to cap).
b)Two sets of 45 degree elbow offsets (bends in flexvent) within the vertical installation. From 0 to a maximum of 8 ft. of vent pipe can be used between elbows.
c)Wall straps must be used to support offset pipe every 4'.
This application will require that you first determine the roof pitch and use the appropriate venting components.
General Maintenance
Conduct an inspection of the venting system
1.Check areas of the venting system which are exposed to the elements for corrosion. These will appear as rust spots or streaks and, in extreme cases, holes. These components should immediately be replaced.
2.Remove the cap and shine a flashlight down the vent. Remove any bird nests or other foreign material.
3.Check for evidence of excessive condensate, such as water droplets forming in the flex venting and subsequently dripping out at joints or seams. Condensate can cause corrosion of caps, pipe and fittings. It may be caused by having excessive lateral runs, or having exterior portions of the system exposed to cold weather.
4.Inspect joints to verify that no pipe sections or fittings have been disturbed and, consequently, loosened. Also, check mechanical supports, such as wall straps or plumbers’ tape for rigidity.
C 24" L MIN.
24"
12" MIN.
MIN.
Figure 10
When terminating the vent cap near an exterior wall or overhang, maintain minimum clearances as shown in Figure 10.
Page 13 |