STANDING PILOT TROUBLESHOOTING

With proper installation and maintenance, your new Gas Fireplace will provide years of trouble-free service. If you do experi- ence a problem, refer to the Trouble Shooting Guide below. This guide will assist a qualified service person in the diagnosis of problems and the corrective action to be taken.

1.Spark ignitor will not light pilot after repeated triggering of piezo ignitor button.

a.Defective ignitor (no spark electrode)

—Check for spark at electrode and pilot; if no spark and electrode wire is properly connected, replace ignitor.

b.No gas or low gas pressure.

—Check remote shut off valves from fireplace. Usually there is a valve near the main. There can be more than one

(1) valve between the fireplace and main.

—Low pressure can be caused by a variety of situations such as a bent line, too narrow diameter of pipe, or low line pressure. Consult with plumber or gas supplier.

c.No LP in tank.

—Check LP (propane) tank. Refill tank.

2.Pilot will not stay lit after carefully following lighting instructions.

a.Defective thermopile.

—Check that pilot flame impinges on thermopile. Clean and/or adjust pilot for maximum flame impingement. —Ensure the thermopile connections at the gas valve are fully tight.

3.Pilot burning, no gas to burner, valve knob “ON.”

a.Wall switch, remote control or wires defective.

—Check wires for proper connections. Place jumper wires across terminal at switch. If burner comes on, replace defective switch. If OK, place jumper wires across switch wires at gas valve-if burner comes on, wires are faulty or connections are bad.

b.Thermopile may not be generating sufficient millivolts. —If the pilot flame is not close enough physically to the thermopile, adjust the pilot flame.

—Be sure the wire connections from the thermopile at the gas valve terminals are tight and the thermopile is fully inserted into the pilot bracket.

—Check the thermopile with a millivolt meter. Take the reading at TH-TP & TP terminals of the gas valve. The meter should read 350 millivolts minimum, while holding the valve knob depressed in the PILOT position, with the pilot lit, and the switch in the OFF position. Replace the faulty thermopile if the reading is below the specified minimum.

—With the pilot in the ON position, disconnect the thermopile leads from the valve. Take a reading at the thermopile leads. The reading should be 350 millivolts minimum. Replace the thermopile if the reading is below the minimum.

c.Defective valve.

—Turn valve knob to ON. Place Remote/Off/On switch to ON. Check with millivolt meter at thermopile terminals. Millivolt meter should read greater than 200 millivolts. If the reading is okay and the main burner does not ignite, replace the gas valve.

d.Plugged main burner orifice.

—Check main burner orifice for blockage and remove.

4.Frequent pilot outage problem.

a.Pilot flame may be too high or too low, or blowing (high), causing pilot safety to drop out.

—Clean and adjust flame for maximum flame impingement on the thermocouple. Follow lighting instructions carefully.

5.The pilot and main burner extinguish while in operation.

a.No LP (Propane) in tank.

Check LP (Propane) tank. Refill fuel tank.

b.Bad thermopile or thermocouple. —Replace if necessary.

c.Improper vent cap installation.

—Check for proper installation and freedom from debris or blockage.

6.(Glass) Sooting

a.Flame impingement on logs.

—Check and adjust log position. Contact Empire Comfort Systems, Inc.

b.Debris around throat of main burner.

—Inspect the opening at the base of the main burner. It is imperative that NO material be placed in this opening.

Page 20

19400-3-0406

Page 20
Image 20
Empire Comfort Systems BVP42FP52, L)N-1 Standing Pilot Troubleshooting, Pilot burning, no gas to burner, valve knob on

BVD34FP50, BVP42FP52, BVP42FP32, BVD34FP30, BVD36FP52 specifications

Empire Comfort Systems has carved a niche in the heating industry with its series of high-quality ventless gas fireplaces. Among their popular models are the BVD34FP50, BVD34FP30, BVD36FP52, BVP42FP52, and BVP42FP32. Each of these units combines sophisticated design with innovative technology, offering home comfort and style.

The BVD34FP50 and BVD34FP30 are known for their sleek appearance and efficient performance. These models feature a minimalist design that allows them to blend seamlessly into any room decor. The BVD34FP50 is equipped with a powerful 50,000 BTU output, making it ideal for larger areas. Conversely, the BVD34FP30, with its 30,000 BTU output, offers an energy-efficient heating solution for smaller spaces. Both models utilize Empire's advanced vent-free technology, which allows for easy installation without the need for traditional venting.

The BVD36FP52 stands out for its versatility in design and efficiency. With a 52,000 BTU capacity, it heats larger spaces effectively while maintaining a sleek and modern visible flame. This model also benefits from an adjustable flame feature, allowing users to customize the intensity to their liking. Its superior ceramic glass front provides excellent heat retention and delivers an unobstructed view of the mesmerizing flames, enhancing any living space.

Empire's BVP42FP52 and BVP42FP32 models further exemplify the brand’s commitment to innovation. The BVP42FP52 offers a robust heating capacity of 52,000 BTUs, while the BVP42FP32 delivers 32,000 BTUs, making both units adaptable for varying room sizes. These models are distinguished by their high-efficiency ceramic glass doors and programmable thermostats, allowing for precise temperature control.

All models are designed with user-friendly features such as remote control options, adjustable flame height, and safety shut-off mechanisms. Additionally, their contemporary aesthetics make them suitable for modern and traditional homes alike. Empire Comfort Systems ensures top-tier reliability and performance, making these fireplaces a worthy investment for all who seek warmth and elegance in their living spaces.