ELECTRICAL TROUBLESHOOTING CHART - HEAT PUMP

ELECTRICAL TROUBLESHOOTING CHART - HEAT PUMP

HEAT PUMPWARNING

ELECTRIC SHOCK HAZARD

Turn off electric power before service or installation.

Extreme care must be used, if it becomes necessary to work on equipment with power applied.

Failure to do so could result in serious injury or death.

SYSTEM COOLS WHEN HEATING IS DESIRED.CAUTION

BURN HAZARD

Certain unit components operate at temperatures hot enough to cause burns.

Proper safety procedures must be followed, and proper protective clothing must be worn.

Failure to do so could result in minor to moderate injury.

HEAT PUMP

SYSTEM COOLS WHEN HEATING IS DESIRED.

Is Line Voltage

Present at the

Solenoid Valve?

YES

NO

Is the Selector Switch Set for Heat?

Is the Solenoid Coil Good?

YES

NO

Replace the Solenoid Coil

Reversing Valve Stuck

Replace the Reversing Valve