Friedrich WS10B10 service manual Problem, Possible Cause, Possible Solution

Models: WS10B10

1 60
Download 60 pages 58.15 Kb
Page 36
Image 36
Manual background

COOLING ONLY ROOM AIR CONDITIONERS: TROUBLESHOOTING TIPS

Problem

Possible Cause

Possible Solution

 

Overload inoperative. Opens too

Check operation of unit. Replace overload if

 

soon

system operation is satisfactory

 

Compressor restarted before

Control board’s default of 3 minutes

 

system pressures equalized

delay inoperative. Replace board.

 

 

 

Compressor runs

 

Check voltage with unit operating. Check for

Low or fluctuating voltage

other appliances on circuit. Air conditioner

for short periods

should be in a dedicated circuit with proper

 

only. Cycles on

 

voltage & fused separately

overload

 

 

Incorrect wiring

Refer to appropriate wiring diagram

 

 

Shorted or incorrect capacitor

Test capacitor and replace as needed.

 

 

 

 

Restricted or low air flow through

Check for proper fan speed or blocked

 

condenser coil or evaporator coil

coils. Correct as needed.

 

Compressor running abnormally

Check for kinked discharge line or restricted

 

condenser. Refrigerant overcharge.

 

hot

 

Check amperage, connections.

 

 

 

 

 

Problem

Possible Cause

Possible Solution

 

No power

Check power supply, LCD I plug, wire

Unit does not

connection.

 

turn on

Incorrect wiring

Refer to appropriate wiring diagram

 

 

Defective thermistor

Replace thermistor or electronic control board

 

 

 

Problem

Possible Cause

Possible Solution

 

Poorly installed

Refer to Installation Manual for proper

 

installation

 

 

 

Fan blade striking chassis

Reposition - adjust motor mount

Noisy operation

 

Check that compressor grommets have not

Compressor vibrating

deteriorated. Check that compressor mounting

 

 

 

parts are not missing

 

Improperly mounted or loose

Check assembly & parts for looseness,

 

cabinet parts

rubbing & rattling

 

 

 

Problem

Possible Cause

Possible Solution

 

Evaporator drain pan overflowing

Clean obstructed drain trough

 

Condensation forming underneath

Evaporator drain pan broken or cracked.

 

Reseal or replace. No chassis gasket installed.

 

base pan

 

Install chassis gasket

 

 

 

Poor installation resulting in rain

Check installation instructions. Reseal as

Water leaks into

entering the room

required

 

Dirty evaporator coil. Use pressure wash

the room

Condensation on discharge grille

or biodegradable cleaning agent to clean.

 

 

louvers

Environmental phenomena: point supply

 

 

louvers upward. Put fan on high.

 

Chassis gasket not installed

Install gasket, per Installation manual

 

Downward slope of unit is too

Refer to installation manual for proper

 

steep inward

installation

35

Page 36
Image 36