Friedrich WS10B10 Coil Sensors, Components Testing, Heat Pump Models, Defrost, Fan Motor

Models: WS10B10

1 60
Download 60 pages 58.15 Kb
Page 14
Image 14
Heat Pump Models

ELECTRONIC CONTROL OPERATION

Heat Pump Models

If the indoor ambient air themister reads 55 degrees or lower, the control will turn off the compressor and turn on the electric heat and continue fan operation until temp setting is satisfied. Then revert to standard heat pump operation.

If the compressor is time delayed, the control will:

1.Turn on the electric heat until the compressor is not time delayed.

2.When the compressor’s 3 minute time delay is over, turn off the electric heat, wait 5 seconds, then turn on the compressor.

Defrost:

If the outdoor coil thermister reads 30 degrees or lower for 2 minutes continuously, the control will turn off the compressor and turn on the electric heat and continue fan operation.

If the outdoor coil thermister reaches 43 degrees and the compressor has waited the standard delay time of

180-240 seconds, the control will:

1.Turn off the backup electric heat

2.Wait 5 seconds

3.Turn on the compressor

4.Continue fan operation.

COIL SENSORS

Positioning of the Coil Sensors (Thermisters) is critical to proper operation of the Electronic Control.

Ensure that sensors are positioned as indicated in the illustrations below.

COMPONENTS TESTING

Defrost:WARNING

ELECTRIC SHOCK HAZARD

Disconnect power to the unit before servicing. Failure to follow this warning could result in serious injury or death.

FAN MOTOR

A single phase permanent split capacitor motor is used to drive the evaporator blower and condenser fan. A self-resetting overload is located inside the motor to protect against high temperature and high amperage conditions. (See Figure 23)

COIL SENSORSWARNING

ELECTRIC SHOCK HAZARD

Disconnect power to the unit before servicing. Failure to follow this warning could result in serious injury or death.

FAN MOTOR - TEST

1.Make sure the motor has cooled down.

2.Disconnect the fan motor wires from the control board.

3.Test for continuity between the windings also, test to ground.

4.If any winding is open or grounded replace the motor.

Fan Motor

13

Page 14
Image 14
Friedrich WS10B10 Coil Sensors, Components Testing, Heat Pump Models, Electronic Control Operation, Defrost, Fan Motor