COOLING ONLY ROOM AIR CONDITIONERS: TROUBLESHOOTING TIPS

Problem

Possible Cause

Possible Solution

 

Low voltage

Check voltage at compressor. 115V & 230V

 

units will operate at 10% voltage variance

 

 

 

Temperature not set cold enough or

Set temperature to lower than ambient

 

room air thermistor inoperative

temperature. Test thermistor and replace

 

 

if inoperative.

 

Compressor hums but cuts off on

Hard start compressor. Direct test compressor.

Compressor

overload

If compressor starts, add starting components

does not run

Open or shorted compressor

Check for continuity & resistance

 

windings

 

 

 

Open overload

Test overload protector & replace if inoperative

 

Open capacitor

Test capacitor & replace if inoperative

 

Inoperative system button

Test for continuity in all positions. Replace if

 

inoperative

 

 

 

Broken, loose or incorrect wiring

Refer to appropriate wiring diagrams to check

 

wiring. Correct as needed.

 

 

Problem

Possible Cause

Possible Solution

 

Inoperative system button

Test button & replace user interface if inoperative

 

Broken, loose or incorrect wiring

Refer to applicable wiring diagram. Repair.

Fan motor

Open capacitor

Test capacitor & replace if inoperative

does not run

Fan speed button defective.

Replace user interface if inoperative

 

Inoperative fan motor

Test fan motor & replace if inoperative (be sure

 

internal overload has had time to reset)

 

 

Problem

Possible Cause

Possible Solution

 

Undersized unit

Refer to industry standard sizing chart

 

Indoor ambient thermistor open

See alarms. Replace thermistor if necessary.

 

or shorted.

 

 

Does not cool or

Dirty filter

Clean as recommended in Owner’s Manual

only cools slightly

Dirty or restricted condenser or

Use pressure wash or biodegradable cleaning

 

evaporator coil

agent to clean

 

Poor air circulation

Adjust discharge louvers. Use high fan speed

 

Low capacity - undercharge

Check for leak & make repair

 

Compressor not pumping properly

Check amperage draw against nameplate. If

 

not conclusive, make pressure test

 

 