SR-18T CLEARANCES
When facing the front of the appliance the following minimum clearances to combustible construction must be maintained.
Left side 6 inches (152mm). Right side 6 inches (152mm). |
|
| |
Do not install in alcove or closet. |
|
| |
Rear wall 0 inches (0mm). Ceiling 36 inches (914mm). |
|
| |
Minimum vertical clearance from a projection above the |
| (914mm) | |
appliance (shelves, window sills, etc.) 36 inches (914mm). |
| ||
|
| ||
Floor (top surface of carpeting, tile, etc.) 2 inches (51mm). | (152mm) | (152mm) | |
Provide adequate clearances around air openings. | |||
|
|
Adequate accessibility clearances for purposes of servicing and proper operation must be provided.
(51mm)
Figure 5 (SR-18T)
SR-30T CLEARANCES
When facing the front of the appliance the following minimum clearances to combustible construction must be maintained.
Left side 8 inches (203mm). Right side 8 inches (203mm). Do not install in alcove or closet.
Rear wall 0 inches (0mm). Ceiling 36 inches (914mm). Minimum vertical clearance from a projection above the appliance (shelves, window sills, etc.) 36 inches (914mm). Floor (top surface of carpeting, tile, etc.) 2 inches (51mm).
Provide adequate clearances around air openings.
Adequate accessibility clearances for purposes of servicing and proper operation must be provided.
36” (914mm)
(203mm) | (203mm) |
Figure 6 (SR-30T)
Page 9 |