Empire Comfort Systems VFP36FP, 31)L(N GAS SUPPLY continued, 36” 2”, Mantel Clearances Figure

Models: VFP32FP VFP36FP P)-1 31)L(N 21)L(N

1 28
Download 28 pages 51.45 Kb
Page 10
Image 10
GAS SUPPLY (continued)

GAS SUPPLY (continued)

Checking Manifold Pressure

VFP(32,36)FP(30,31)LN (Natural gas) will have a manifold pressure of approximately 3.5" w.c. (.871kPa) for maximum input or 1.7" w.c. (.423kPa) for minimum input at the pressure regulator outlet with the inlet pressure to the pressure regulator from a minimum of 4.5" w.c. (1.120kPa) for the purpose of input adjustment to a maximum of 10.5" w.c. (2.614kPa). VFP(32,36)FP(20,21)LN (Natural gas) will have a manifold pressure of approximately 6.0" w.c. (1.49kPa) at the pressure regulator outlet with the inlet pressure to the pressure regulator from a minimum of 7.0" w.c. (1.74kPa) for the purpose of input adjustment to a maximum of 10.5" w.c. (2.615kPa). VFP(32,36)FP(30,31)LP (Propane gas) will have a manifold pressure approximately 10.0"w.c. (2.49kPa) for maximum input or 4.9"w.c. (1.220kPa) for minimum input at the pressure regulator outlet with the inlet pressure to the pressure regulator from a minimum of 11.0"w.c. (2.739kPa) for the purpose of input adjustment to a maximum of 13.0"w.c. (3.237kPa).

VFP(32,36)FP(20,21)LP (Propane gas) will have a manifold pressure approximately 10.0"w.c. (2.49kPa) at the pressure regulator outlet with the inlet pressure to the pressure regulator from a minimum of 11.0"w.c. (2.739kPa) for the purpose of input adjustment to a maximum of 13.0"w.c. (3.237kPa).

A test gage connection is located downstream of the gas appliance pressure regulator for measuring gas pressure. The connection is a 1/8 inch (3mm) N.P.T. plugged tapping.

VFP(32,36)FP(30,31) Millivolt Control

The valve regulator controls the burner pressure which should be checked at the pressure test point. Turn captured screw counter clockwise 2 or 3 turns and then place tubing to pressure gauge over test point (Use test point “A” closest to control knob). After taking pressure reading, be sure and turn captured screw clockwise firmly to re-seal. Do not over torque. Check for gas leaks.

CLEARANCES

Minimum Wall and Ceiling Clearances (Figure 4)

Sidewall Clearances: The clearance from the inside of the fireplace to any combustible wall should not be less than 2".

Fireplace Side and Back Clearances: The fireplace outer casing sides and back have zero clearance to combustibles.

Ceiling Clearances: The ceiling height should not be less than 36" from the top of the hood.

Mantel Clearances: Vent free fireplace models must use the hood supplied with the fireplace. If a combustible mantel is installed, it must meet the clearance requirements detailed above.

36”

Checking Manifold Pressure 2” VFP(32,36)FP(30,31) Millivolt Control

Mantel Clearances (Figure 5)

CLEARANCES 12” Minimum Wall and Ceiling Clearances (Figure 4) 10” 36”

MANTEL

COMBUSTIBLES

ALLOWED Mantel Clearances (Figure 5) 8” Manual background

Manual background 6” Manual background

18”4”

15 1/4”

12 ½”

2”

 

9 3/4”

7”

4 1/4”

HOOD Manual background

Figure 5

Figure 4

Page 10

20101-0-0306

Page 10
Image 10
Empire Comfort Systems VFP36FP, VFP32FP, 31)L(N, P)-1 GAS SUPPLY continued, Clearances, 36” 2”, Checking Manifold Pressure