SmartValve™ System Troubleshooting Sequence

DVC-35IPT INTERMITTENT PILOT SYSTEM TROUBLESHOOTING SEQUENCE

START

Turn OFF Gas Supply

Disconnect System Control Harness

Set Thermostat to Call for Heat

Check for Proper Voltage at Control Harness (See Inset A -Voltage Should be 24V Between Thermostat and 24V Common, and 24V Between 24V Common and 24V Hot.)

YES

Plug Harness into SmartValve Control

Wait for Internal Check Delay (SV9501)

SmartValve™ System Troubleshooting Sequence

Note: Before Troubleshooting, Become Familiar

with the Sequence of Operation

 

CHECK

 

Line Voltage Power

NO

Low Voltage Transformer

Limit Controller

 

 

Thermostat

 

Wiring

 

 

 

 

INSET A

End View

24Volt

 

of Control

Thermostat

 

Harness

 

 

Connector

24

 

EFT

Volts

 

Output

24 Volt

24

24 Volt

Common

Hot

 

Volts

 

INSET B

HSI

 

 

 

 

Terminals

 

Igniter Warms UP and Glows Red

Note: Igniter Will Cycle OFF

and Back ON Once During

the 90 Second Ignition Trial

YES

NO

Unplug Pilot Burner Cable.

Measure Voltage at SmartValue

HSI Element Output (See Inset B)

24V Nominal

Note: Before Troubleshooting, Become Familiar YES

Replace Igniter/Flame Rod Assembly

Reconnect Pilot Burner Cable

NO

with the Sequence of Operation Replace SmartValve Control

Reconnect Pilot Burner Cable

Turn On Gas Supply

Pilot Burner Lights

YES

Main Valve Opens and Main Burner Lights

YES

System is Okay

NO

NO

Check that Pilot Gas is Flowing Wait to Assure Pilot Gas Tubing is Purged.

Manual background YES

Measure Voltage Between 24V Hot and 24V Common Leads to SmartValve Control. Must Measure at Least 19.5 VAC with Igniter Powered. See Inset A to Identify Proper Lead. This Check Must be Done with the SmartValve Control Connected and Igniter Powered.

Manual background YES

Replace Igniter/Flame Rod Assembly

Check that Pilot Flame Makes Good Contact with Pilot Burner Flame Rod

Check for Good Electrical Connection Through the Pilot Tubing

If Both of the Above are Good, Replace Igniter/Flame Rod

Cycle Thermostat OFF and Back ON

Main Burner Lights

NO

Replace SmartValve Control

NO

Check Transformer and Line

 

 

Volt Supply

NO

Replace SmartValve Control

 

13119-6-0107