Empire Products DVC-35IPT-1, DVC-35T-1 Clearances, Figure Checking Manifold Pressure

Models: DVC-35T-1 DVC-35IPT-1

1 24
Download 24 pages 12.73 Kb
Page 8
Image 8
Figure 3

Figure 3

Checking Manifold Pressure

Both Propane and Natural gas valves have a built-in pressure regulator in the gas valve. Natural gas models will have a manifold

pressure of approximately 4.0” w.c. (.996kPa) for DVC-35T and 3.5” w.c. (.871kPa) for DVC-35IPT at the valve outlet with the inlet pressure to the valve from a minimum of 5.0” w.c. (1.245kPa) for the purpose of input adjustment to a maximum of 7.0” w.c. (1.743kPa). Propane gas models will have a manifold pressure approximately 10.0” w.c. (2.49kPa) at the valve outlet with the inlet pressure to the valve from a minimum of 11.0” w.c. (2.739kPa) for the purpose of input adjustment to a maximum of 13.0” w.c. (3.237kPa).

A1/8” N.P.T. plugged tapping, accessible for test gauge connection, is located on the outlet side of the gas control.

The built-in regulator comes on at approximately 1/4th pressure and full on in 10 seconds.

CLEARANCES

Clearances

1.In selecting a location for installation, it is necessary to provide adequate accessibility clearances for servicing and proper installation. A front clearance of 36” is recommended. Do not block outlet or inlet air openings on the front grill.

2.The DV4T-59-1, 5” to 9” wall depth is the standard vent kit provided with the DVC-35T orDVC-35IPT. SeeAccessories Page 6 to order vent kits for wall depths of 8” to 12” or 12” to 19”. The use of tubes not supplied by the manufacturer results in unsatisfactory performance.

3.The DVC-35T and DVC-35IPT can be attached to the wall or recessed into the wall up to 9 1/2” in depth but the minimum 5” vent/air intake system wall depth must be maintained. Example: If furnace is recessed into the wall at a depth of 9 1/2”, the minimum wall depth behind the furnace must be 5”.

4.The wall in which the furnace is recessed has (0) zero clearance to the furnace sides and top.

5.When using side discharge registers, SOR-1 or SOK-1, the furnace cannot be recessed into the wall.

6.Clearance to sidewall or combustible material is 4”.

7.Ceiling clearance is 4”.

8.Floor and rear wall clearance is (0) zero inches.

9.Clearance of 18” is required to sidewall or combustible material when flush mounted SOR-1, side outlet register is used.

10.The minimum distance from the center of the vent cap to the nearest outside corner or obstruction is 12”.

Figure 4

The vent terminal of this direct vent appliance shall be located at least 9” from any opening through which flue gases could enter a building. The bottom of the vent terminal and the air intake shall be located at least 12” above grade. See vent location, Figure 4.

WARNING: The nearest point of the vent cap should be a minimum horizontal distant of six (6) feet from any pressure regulator. In case of regulator malfunction, the six (6) feet distance will reduce the chance of gas entering the vent cap.

Page 8

13119-6-0107

Page 8
Image 8
Empire Products DVC-35IPT-1, DVC-35T-1 installation instructions Clearances, Figure Checking Manifold Pressure