VENT SAFETY SHUTOFF SYSTEM

VENT SAFETY SHUTOFF SYSTEM

This appliance must be properly connected to a venting system.

This appliance is equipped with a vent safety shutoff system.

Warning: Operation of this wall furnace when not connected to a properly installed and maintained venting system or tampering with the vent safety shutoff system can result in carbon monoxide (CO) poisoning and possible death.

This furnace is equipped with a manual reset vent safety switch. The manual reset vent safety switch will cause gas flow to the main burner to "shut off" due to improper venting or a blocked flue.

To reset the manual reset vent safety switch:

1.Remove outer casing.

2.Depress manual reset button. The manual reset vent safety switch is located on the draft diverter.

3.Replace outer casing.

If the manual reset vent safety switch continues to "shut off" the gas flow to the main burner a qualified service person must be contacted to inspect for improper venting, blockage in the vent pipe or the manual reset vent safety switch for being defective.

Figure 8

PROPER MAIN BURNER FLAME

The correct flame will be a short blue inner flame with a much larger light blue outer flame. The burner does not have a primary air adjustment. The flame will be proper if the factory-set pressure and orifice are used. After the furnace has begun operating, cleaning of the burner may be needed for proper flame, examine at least 2 times per season.

To clean burner ports, disconnect the gas supply to the valve. Remove

 

the burner assembly from the combustion chamber. Remove pilot

 

burner from main burner and then remove the main burner. Force

 

water into the ports and blow dry with vacuum cleaner air, or low

Figure 9

pressure compressed air.

PROPER PILOT FLAME

 

The correct flame will be blue, extending past the thermopile. The

 

flame will surround the thermopile just below its tip.

 

Natural gas pilots require adjusting when the inlet gas pressure is

 

above 5" w.c. (1.245kPa). Remove the pilot cover screw on the

 

control valve and turn the adjustment screw clockwise to reduce

 

flame. Replace pilot cover screw to eliminate gas leaking at that

 

control valve opening.

 

LP gas (propane) will not require adjustment.

 

After use, cleaning may be required for the proper flame.

 

Examine the pilot flame before and during each heating season.

Figure 10

 

12425-10-1008

Page 13

Page 13