035-18496-000-C-1102

 

 

INDOOR PRODUCT NOMENCLATURE

 

 

 

 

L A 300 C 00 A 6 A AA 1

 

 

 

 

 

 

Model #

Model Number

 

Options

 

Description

 

 

 

 

 

 

 

L

Product Category

 

L = Air Handling Unit

 

 

 

 

 

 

A

Product Identifier

 

A = R-22 Standard Efficiency 2-Pipe

 

 

B = R-22 Standard Efficiency 4-Pipe

 

 

 

 

 

 

 

 

 

 

 

Nominal Cooling

 

300 = 25 Ton

 

 

 

360 = 30 Ton

 

300

Capacity

 

 

 

480 = 40 Ton

 

 

MBH

 

 

 

 

600 = 50 Ton

 

 

 

 

 

 

 

 

 

 

C

Heat Type

 

C = Cooling Only

 

 

 

 

 

 

00

Nominal Heating

 

00 = No Heat Installed

 

Capacity

 

 

 

 

 

 

 

 

 

 

 

 

A

Airflow Options

 

A = None

 

 

 

 

 

 

6

Voltage

 

5 = 575-3-60

6 = 208/230-460-3-60

 

 

 

 

 

A

Installation Options

 

A = None

 

 

 

 

 

 

AA

Additional Options

 

AA = None

 

 

 

 

 

 

1

Product Generation

 

1 = First Generation

2 = Second Generation

 

 

 

 

 

NOTE: LB600 Indoor Unit matches with both HB480 and HB600 Outdoor Condensing Units for maximum efficiency.

TABLE 1: UNIT APPLICATION DATA

 

 

 

 

 

 

Entering Air Temperature Degrees °F

Model

Power Supply Voltage

Voltage Variation

Supply Air Range CFM

Cooling

Heating DB*

 

 

 

 

DB/WB

 

 

 

 

 

 

 

 

 

 

 

 

Min.

Max.

Min.

Max.

Min.

Max.

Min.

Max.

 

208/230-3-60

187

253

8,000

12,000

65/57

95/72

40

77

LA300

460-3-60

414

506

8,000

12,000

65/57

95/72

40

77

 

575-3-60

540

630

8,000

12,000

65/57

95/72

40

77

 

208/230-3-60

187

253

10,000

14,000

65/57

95/72

40

77

LB360

460-3-60

414

506

10,000

14,000

65/57

95/72

40

77

 

575-3-60

540

630

10,000

14,000

65/57

95/72

40

77

 

208/230-3-60

187

253

12,800

19,200

65/57

95/72

40

77

LB480

460-3-60

414

506

12,800

19,200

65/57

95/72

40

77

 

575-3-60

540

630

12,800

19,200

65/57

95/72

40

77

 

208/230-3-60

187

253

16,000

24,000

65/57

95/72

40

77

LB600

460-3-60

414

506

16,000

24,000

65/57

95/72

40

77

 

575-3-60

540

630

16,000

24,000

65/57

95/72

40

77

*. Heating Min/Max temperatures apply to steam and hot water coils. NOTE: Do not apply steam to hot water coils.

Unitary Products Group

5

Page 5
Image 5
Energy Tech Laboratories LB360, LB480, LB300, LB600 installation manual Mbh, Unit Application Data