035-18496-000-C-1102

NON-FLAMMABLE COLLAR

24"

DUCT TRANSITION

DUCT

AIR

 

OUTLET

 

 

FLANGED DUCT

BLOWER

CONNECTION

(FIELD

GASKETS

FABRICATED)

(BY INSTALLER)

 

FIGURE 13 - SUGGESTED METHOD FOR CONNECTING DUCTWORK

RETURN AIR DUCT ANGLES

Return air duct angles are shipped turned in. They are intended to be unscrewed and turned for connection of duct- work. The return air grille accessory attaches in the same manner as the panels.

DRAIN CONNECTIONS

All drain lines MUST be trapped and located so they will not be exposed to freezing temperatures.

The evaporator blower has 7/8" OD steel condensate stub at each end of a single drain pan. Both ends are closed with plastic caps. A plastic or rubber ell can be used. (Field sup- plied) Attach the ell to the desired end and run a full size 7/8" drain line to the nearest drain facility. Seal the cap at the unused end with suitable mastic.

Drain piping should be constructed as shown in 14. The 3- inch dimension must equal or exceed the negative static pressure developed by the supply air blowers. If it does not, the condensate will not drain properly and may overflow the drain pan. The trap must be at least 2-inches deep to main- tain a water seal under all operating conditions, especially when the blowers are starting.

FIGURE 14 - RECOMMENDED DRAIN PIPING REFRIGERANT MAINS

Hard drawn copper tubing should be used where no appre- ciable amount of bending around pipes or other obstructions is necessary. Use long radius ells wherever possible. If soft copper is used, care should be taken to avoid sharp bends that may cause a restriction.

Where refrigerant lines pass through a wall, pack fiberglass insulation and a sealing material such as permagum around the refrigerant lines to reduce vibration and to retain some flexibility in the lines.

16

Unitary Products Group

Page 16
Image 16
Energy Tech Laboratories LB480, LB360, LB300, LB600 installation manual Return AIR Duct Angles, Drain Connections