Energy Tech Laboratories MR212 manual Heater Start Up Summary

Models: MR212

1 28
Download 28 pages 2.84 Kb
Page 13
Image 13

Heater Start Up Summary

Is incoming gas pressure

No

Adjust

7"-14"?

incoming gas

 

 

(7"-5 psi. for size 4-5 units)

 

 

pressure.

 

 

 

 

Yes

Adjust pilot flame.

Lock unit into

high fire.

Does high fire produce

 

No

at least a 70°F temp

 

 

rise and produce the

 

Adjust high fire

 

correct manifold

 

 

pressure?

 

 

 

 

 

 

 

Yes

 

 

 

 

 

Lock unit into low fire.

Does thin flame fill

No

 

Adjust low

entire burner length?

 

fire.

 

 

 

Yes

Burner start up

complete.

Setting incoming pressure:

Presure must be measured at first "T" in supply gas line before the first gas valve.

Adjusting the pilot:

The pilot DC signal should be 12 VDC minimum.

Adjusting high fire:

High fire manifold pressure should be 5" maximum for natural gas and 2.5" maximum for propane. High fire should produce at least a 70°F temperature rise. Remove wire #4 from the Maxitrol 14 amplifier (#2 and #4 for Maxitrol 44). This will drive the valve into its full open position. Adjust high fire with the regulator inside the unit. Turn clockwise to increase temperature rise. Ensure that DC flame signal is minimum 12 VDC. Replace the wires on the Maxitrol Amplifier.

Adjusting low fire:

Remove wire #5 from the Maxitrol 14 amplifier (#8 for Maxitrol 44). This will drive the valve into its lowest position.

Adjust the low fire by turning the low fire bypass screw on the side of teh modulating valve for M511 and M611 models. For MR212 valves, the low and high fire are both under the valve cover. Refer to the included Maxitrol literature for more detailed information. Ensure that DC flame signal is minimum 12 VDC and that the enite length of burner is filled with a thin flame.

13

Page 13
Image 13
Energy Tech Laboratories MR212 manual Heater Start Up Summary, Yes Adjust pilot flame Lock unit into High fire