Initial Installation
QUALIFIED INSTALLERS ONLY
CONVERTING A DIRECT VENT FIREPLACE TO A B-VENT FIREPLACE:
1.Remove the Direct Vent chimney connector assembly by taking out the two (2)
2.Remove the two (2) fresh air inlet covers from each side. Cover locations shown in Figure 16.
3.Slide the
4.Disconnect the two (2) blue wires at the opening to the right of the unit and connect them to the 300°F (149°C) manual reset spill switch at the rear of the
5.Test fire the appliance and ensure proper operation. A venturi adjustment could be required to achieve an efficient flame. Improper operation or adjustment could result in Carbon Monoxide production causing personal injury or property damage.
Direct Vent |
Connector Assembly |
Fresh Air |
Inlet Covers |
Figure 16: Converting to a BV fireplace.
Connector Assembly |
300°F (149°C) |
manual reset |
spill switch |
Figure 17: Converting to a BV fireplace.
17