Enviro 50-1096, C-10637 owner manual Initial Installation, Clearances to Combustibles

Models: C-10637 50-1096

1 31
Download 31 pages 45.57 Kb
Page 11
Image 11

Initial Installation

WARNING: Operation of this heater when not connected to a properly installed and maintained venting system can result in carbon monoxide (CO) poisoning and possible death.

CLEARANCES TO COMBUSTIBLES:

Maintain sufficient clearances for operation, service and maintenance.

• A clearance of 25 1⁄2” (648 mm) minimum is required from the center of the unit to the sidewalls.

A 2” (51 mm) wide mantel can be mounted at a minimum height of 39” (991 mm) from the bottom of unit.

A 10” (254 mm) wide mantel can be mounted at a minimum height of 43” (1092 mm) from the bottom of unit.

If installed at floor level, a minimum 16” (406 mm) non-combustible material must be installed in front of the unit.

If installed on a 12” (305 mm) wide hearth raised a minimum height of 6” (152 mm), no floor protection is required.

Refer to Figure 9 for additional required floor protection dimensions with different width hearths.

 

10" (254mm) Mantle

2" (51mm)

 

Mantle

 

39" (991 mm)

43" (1092 mm)

minimum to

minimum to

bottom of unit

bottom of unit

Figure 8: Mantle width and height.

 

12" (305mm)

11" (279mm)

 

 

 

 

6" (152mm)

 

 

 

 

 

 

Sienna

EXAMPLE: If the Sienna is raised

 

 

 

 

 

 

 

 

 

 

 

 

 

6" (152mm) and has 4" (102mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

wide hearth in front of it then

12"

 

 

 

 

 

 

 

 

 

 

 

 

 

(305mm) of non-combustible

 

 

 

 

 

 

 

 

 

 

 

 

 

 

floor protection is require to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

be installed in front of the

 

 

 

 

 

 

 

 

 

 

 

 

 

Hearth Height

hearth.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

of 6" (152mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(0mm)0"

 

(127mm)

(152mm)

(178mm)

(203mm)

(229mm)

(254mm)

(279mm)

(305mm)

(330mm)

(356mm)

(381mm)

(406mm)

Non-combustible

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

floor protection required

 

 

 

 

 

 

 

 

 

 

 

 

 

 

in front of corresponding

 

 

5"

6"

7"

8"

9"

10"

11"

12"

13"

14"

15"

16"

hearth width

 

 

 

Figure 9: Floor protection distance required.

If the unit is to be installed into a zero clearance fireplace the metal floor may be removed to facilitate the installation. The stove may be installed on a combustible material if a minimum 20-gauge piece of

steel is installed under the unit. The sides and top of the structure can not be altered though baffles and dampers can be removed.

WARNING: This fireplace cannot be used for burning wood or solid fuels unless all original parts have been replaced and the fireplace is re-approved by the authority having jurisdiction.

11

Page 11
Image 11
Enviro 50-1096, C-10637 owner manual Initial Installation, Clearances to Combustibles