Enviro C-10791, 50-927 owner manual Initial Installation, Qualified Installers Only

Models: 50-927 C-10791

1 35
Download 35 pages 2.68 Kb
Page 18
Image 18
restrictor is located in the center of the

Initial Installation

QUALIFIED INSTALLERS ONLY

VENT CONFIGURATIONS AND RESTRICTOR SETTINGS:

Figures 23 shows the range of venting options, it shows possible vent configurations if the unit is top vented, for vertical and horizontal terminations, any layout that remains within the shaded area is acceptable. Having the fewest number of elbows is ideal, as they tend to disrupt air movement. Using 45˚ elbows is preferable to using 90˚ elbows. Also, a shorter vent system will perform better than a longer one.

The vent restrictor controls the amount of air moving through the vent pipe. Longer vertical vent lengths necessitate greater restriction; position 1 is open and position 5 is maximum restriction. Figure 23 shows the vent restrictor position required,

NOTE: The total length of the vent pipes can

relative to the length of vent pipe. The vent

not exceed 32 feet (15.12 m). Any combination

restrictor is located in the center of the

of rise and run can be used as long as it lays

fireplace, above the glass. Figure 24 shows

within the shaded area (a total of three (3) 90°

elbows or six (6) 45° elbows can be used).

the vent restrictor dial and the holes that

In addition to what is shown, if a 90°

indicate the different levels. To avoid injury,

elbow is used in the horizontal plane,

it is best to make this adjustment when the

3 feet (91.4 cm) must be subtracted

fireplace is cool or use welder’s gloves or

from the allowable horizontal run

(for each 45° elbow, 11⁄2 feet

oven mitts.

must be subtracted from the

Note: 0,0 in Figure 23 represents a 90˚

allowable horizontal run).

 

bend directly off the outlet of the unit, 413⁄4

 

inches (106 cm) from floor, in all horizontal

 

instances except when using Selkirk and

 

having less than a 4 feet (1.22 m) rise and

 

8 feet (2.44 m) horizontal offset. In this

 

case, a 1 foot (30.5 cm) rise must be added

 

below the 90˚ bend.

 

Note for rear vented: At 293⁄8 inches (75

 

cm) up, the maximum horizontal rear exit

 

vent length is 17 inches (43 cm) with a 45°

 

elbow (see Figure 12).

Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background

Figure 23. Possible Vent Configurations for Top Vented; Vertical Figure 24. Possible Vent Restrictor Positions. and Horizontal Terminations.

18

Page 18
Image 18
Enviro C-10791, 50-927 Initial Installation, Qualified Installers Only, restrictor is located in the center of the