Initial Installation
QUALIFIED INSTALLERS ONLY
VENT CONFIGURATIONS AND RESTRICTOR SETTINGS:
Figures 23 shows the range of venting options, it shows possible vent configurations if the unit is top vented, for vertical and horizontal terminations, any layout that remains within the shaded area is acceptable. Having the fewest number of elbows is ideal, as they tend to disrupt air movement. Using 45˚ elbows is preferable to using 90˚ elbows. Also, a shorter vent system will perform better than a longer one.
The vent restrictor controls the amount of air moving through the vent pipe. Longer vertical vent lengths necessitate greater restriction; position 1 is open and position 5 is maximum restriction. Figure 23 shows the vent restrictor position required,
NOTE: The total length of the vent pipes can | relative to the length of vent pipe. The vent |
not exceed 32 feet (15.12 m). Any combination | restrictor is located in the center of the |
of rise and run can be used as long as it lays | fireplace, above the glass. Figure 24 shows |
within the shaded area (a total of three (3) 90° | |
elbows or six (6) 45° elbows can be used). | the vent restrictor dial and the holes that |
In addition to what is shown, if a 90° | indicate the different levels. To avoid injury, |
elbow is used in the horizontal plane, | it is best to make this adjustment when the |
3 feet (91.4 cm) must be subtracted | fireplace is cool or use welder’s gloves or |
from the allowable horizontal run | |
(for each 45° elbow, 11⁄2 feet | oven mitts. |
must be subtracted from the | Note: 0,0 in Figure 23 represents a 90˚ |
allowable horizontal run). | |
| bend directly off the outlet of the unit, 413⁄4 |
| inches (106 cm) from floor, in all horizontal |
| instances except when using Selkirk and |
| having less than a 4 feet (1.22 m) rise and |
| 8 feet (2.44 m) horizontal offset. In this |
| case, a 1 foot (30.5 cm) rise must be added |
| below the 90˚ bend. |
| Note for rear vented: At 293⁄8 inches (75 |
| cm) up, the maximum horizontal rear exit |
| vent length is 17 inches (43 cm) with a 45° |
| elbow (see Figure 12). |
�� �� �
Figure 23. Possible Vent Configurations for Top Vented; Vertical Figure 24. Possible Vent Restrictor Positions. and Horizontal Terminations.
18