Enviro DV36 owner manual Initial Installation, Qualified Installers Only, fireplace, certain

Models: DV36

1 40
Download 40 pages 5.01 Kb
Page 21
Image 21
fireplace, certain

Initial Installation

QUALIFIED INSTALLERS ONLY

VENTING:

This fireplace has been tested and certified for use with SIMPSON DURAVENT DIRECT VENT TYPE “GS” PIPE FOR GAS STOVES, SECURITY CHIMNEY’S SECURE VENT DIRECT VENT SYSTEM kits, AMERICAN METAL PRODUCTS AMERIVENT DIRECT and DIRECT-TEMP SELKIRK METALBESTOS.

A 1” (25 mm) clearance to combustibles must be maintained around any vertical vent pipe. Around a horizontal vent pipe, the clearance to combustibles should be 2” (51 mm) above and 11⁄2” (38 mm) on the sides and bottom. When combustible materials are directly above a 90° elbow, 3” (76 mm) of clearance are necessary (see Figure 28).

Table 7. Vent Pipe Minimum Clearances.

 

Vertical Pipe to

Horizontal Pipe to

Above an Elbow

Above an Elbow

Above Horizontal

Wall Frame 8”

 

the Side Walls

the Sides & Bottom

Above the Unit

Not Above the Unit

Vent Pipe

(203mm) or less

 

 

 

 

 

 

 

Hard

1”

11⁄2”

3”

3”

2”

10”x10”

Pipe

(25.4 mm)

(38.1 mm)

(76.2 mm)

(76.2 mm)

(51 mm)

(25x25cm)

 

 

 

 

 

 

 

Flex

1”

11⁄2”

8”

4 3⁄8”

4 3⁄8”

10”x10”

Pipe

(25.4 mm)

(38.1 mm)

(203 mm)

(111 mm)

(111 mm)

(25x25cm)

 

 

 

 

 

 

 

A 10” (254 mm) x 10” (254 mm) frame (see Figure 29) will assure the proper support and spacing for the vent pipe as it passes through the wall. Installations in Canada require that a wall thimble be used for passing through walls and ceilings. All sealing and vapour barriers must comply with local building codes.

When planning an installation, it is necessary to select the proper length of vent pipe for the particular requirements. The configuration of the venting pipes depends on the locations of walls, ceilings, and studs. However, the pipes cannot be of arbitrary length and arrangement. Because the length of the vertical and horizontal

sections dramatically affects the burning efficiency of the

fireplace, certain

guidelines have been set in INITIAL

INSTALLATION - VENT

CONFIGURATIONS AND

RESTRICTOR SETTINGS.

A two (2) piece wall/

Figure 29. Vent Framing For Wall or Ceiling. ceiling thimble is

included with the stove (see Figure 30).

Venting terminals can not be recessed into a wall or siding.

2" (51mm)

3" (76mm)

 

41 3/4"

 

(1048mm)

 

Figure 28. Vent Pipe Clearances.

WARNING: This gas appliance must not be connected to a chimney flue serving a separate solid-burning appliances.

Figure 30. Wall/Ceiling Thimble provided.