Initial Installation
WARNING: Operation of this heater when not connected to a properly installed and maintained venting system can result in carbon monoxide (CO) poisoning and possible death.
CLEARANCES TO COMBUSTIBLES:
Maintain sufficient clearances for operation, service and maintenance.
• A clearance of 25 1⁄2” (648 mm) minimum is required from the center of the unit to the sidewalls.
•A 2” (51 mm) wide mantel can be mounted at a minimum height of 39” (991 mm) from the bottom of unit.
•A 10” (254 mm) wide mantel can be mounted at a minimum height of 43” (1092 mm) from the bottom of unit.
•If installed at floor level, a minimum 16” (406 mm)
•If installed on a 12” (305 mm) wide hearth raised a minimum height of 6” (152 mm), no floor protection is required.
•Refer to Figure 9 for additional required floor protection dimensions with different width hearths.
| 10" (254mm) Mantle |
2" (51mm) |
|
Mantle |
|
39" (991 mm) | 43" (1092 mm) |
minimum to | minimum to |
bottom of unit | bottom of unit |
Figure 16: Mantle width and height.
| 12" (305mm) | 11" (279mm) |
|
|
|
| 6" (152mm) |
|
|
|
|
|
| Sienna |
EXAMPLE: If the Sienna is raised |
|
|
|
|
|
|
|
|
|
|
|
|
| |
6" (152mm) and has 4" (102mm) |
|
|
|
|
|
|
|
|
|
|
|
|
| |
wide hearth in front of it then | 12" |
|
|
|
|
|
|
|
|
|
|
|
|
|
(305mm) of |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
floor protection is require to |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
be installed in front of the |
|
|
|
|
|
|
|
|
|
|
|
|
| Hearth Height |
hearth. |
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
| of 6" (152mm) | |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
(0mm)0" |
| (127mm) | (152mm) | (178mm) | (203mm) | (229mm) | (254mm) | (279mm) | (305mm) | (330mm) | (356mm) | (381mm) | (406mm) | |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
| floor protection required |
|
|
|
|
|
|
|
|
|
|
|
|
|
| in front of corresponding |
|
| 5" | 6" | 7" | 8" | 9" | 10" | 11" | 12" | 13" | 14" | 15" | 16" | hearth width |
|
|
|
Figure 17: Floor protection distance required.
13