2-6 Dip Switches

Dip switch number 2 (CF Card interface cover access control)

When the dip switch number 2 is set to the ON position, access to the CF card is possible

Caution whether the cover is opened or not. In case access to the CF card is disabled because of damage of the CF card interface cover, set the dip switch number 2 to the ON position.

Normally keep it in the OFF position.

With the dip switch number 2, the LED status when the CF card interface cover is opened can be set.

Dip switch number 2

LED

Contents

 

Not lit

Access to the CF card is not performed.

 

CF card can be removed.

OFF

 

 

 

Lights up in red

Accessing the CF card.

 

 

After the access is finished, the LED goes off.

 

 

 

 

 

ON

Lights up in red

Access to the CF card is possible at all times.

 

 

 

Dip switch number 3, 4 (Not used)

Set the dip switch number 3 and 4 to OFF.

Dip switch number 5, 6, 7, 8 (Terminating resistor setting)

Caution

When connecting a controller at CN1 via RS-232C, set the dip switch number 5 and 7 to the

OFF position.

 

 

When connecting a controller at CN1 via RS-422/485 (2-wire connection), set the dip switch number 7 to the ON position.

When connecting a controller at CN1 via RS-422/485 (4-wire connection), set the dip switch number 5 and 7 to the ON position.

For the following connections at modular jack 1 or 2, set the dip switch number 6 or 8 to the ON position.

Master station for multi-link 2 connection

Connection with a controller (PLC, temperature controller, etc.) via RS-485

Connection with the card recorder “CREC” (optional)

Connection with the serial extension I/O “V-I/O” (optional)

Connection to the @E.Terminal at the termination of V-Link connection via RS-485

*Detaching controller unit

To operate the dip switch in NP5M0101-5H4/4H4, NP5N0011-5H4/4H4, remove the controller unit. Remove mounting screws at three places to remove the controller unit from the display unit.

Be careful not to drop or lose the mounting screws.

Mounting screws at three places M3 screws thread, Tightening torque:

0.5 to 0.7N·m

 

 

CN7

CN5

 

 

SX-BUS

ONL

 

ERR

 

IN

UROM

 

ALM

 

 

RUN

 

 

BAT

 

 

4:RUN

 

 

3:U-TERM

 

 

2:TERM

 

 

1:STOP

 

 

CPU

 

 

No.

 

OUT

 

 

+

 

 

24V DC

 

-

 

 

FG

 

CF

 

USER ROM CARD

USB

LOADER

MJ1

MJ2

CN1

LAN

U-B

U-A