Flow Meter FC01-LQ
8.5 Metrological data
8.5.1 Flow rate measurement
Measuring is possible up to the flow rates indicated in the display range. However, the indicated accuracy is no longer guaranteed. The repeatability value remains valid.
8.5.1.1 Monitoring head CSP- with sensor adapter type TP-..
Flow rate measurement:
Sensor adapter | Measuring range | Display range | ||
type |
| in m3/h | in m3/h | |
TP01 | 0.02 | … | 2.2 | 2.9 |
TP02 | 0.04 | … | 3.4 | 4.5 |
|
|
|
|
|
TP03 | 0.05 | … | 5.3 | 7.1 |
|
|
|
|
|
TP04 | 0.1 | … | 8.7 | 11.6 |
|
|
|
| |
TP05 | 0.14 | … 13.6 | 18.1 | |
|
|
|
| |
TP06 | 0.2 | … 21.2 | 28.3 | |
|
|
|
|
|
8.5.1.2 Monitoring head CSF
Flow measurement ranges:
The flow measurement range is determined by the inner pipe diameter (see table). It can be calculated with the following equation:
Q = VN x AR
Q [m3/h] - flow quantity
VN [m/h] - average standard velocity
AR [m2] - inner pipe
Technical data | 53 |