6Boost Mode - The AVR is increasing the UPS output voltage due to a low utility voltage condition or "Brown-out". The sinewave symbol is also displayed to indicate that the UPS is operating normally from the utility line.

7.Timer is enabled - This symbol will be displayed during the following conditions:

a)The UPS has been programmed to automatically turn on or off using the supplied remote monitoring software.

b)The green mode is enabled and the UPS output load is under 25 watts. The UPS will turn off after a 30 second delay.

8.Over Temperature - The temperature inside the UPS has exceeded 55ºC. If the end-user does not reduce the UPS output load or correct the cause of the UPS overheating, the temperature will continue to rise and upon reaching 60ºC the UPS will shutdown to prevent damage due to excessive overheating.

9.Fan off - This symbol is used on special extended backup models only.

10.Alarm off - The audible alarm has been silenced. To reset the alarm during backup mode, briefly depress the control button.

11.UPS fault - Attempt to perform a UPS reset by depressing the control button and holding it for ten seconds. If the UPS resets and operates normally, no further action is required. If the UPS fault indicator is still displayed, the UPS has failed and must be repaired.

12.Battery low - When the battery charge level is low, the word "LOW" will be displayed inside the battery normal symbol.

13.Battery normal - During normal utility operating this symbol indicates a charged battery.

14.Battery level - When the battery is fully charged, all five bar graph segments will be dark. As the battery discharges, the segments will disappear starting from the top segment and end with the bottom segment.