OPTIONAL GSK-3 EXHAUST GAS SPILLAGE DETECTOR SWITCH INSTALLATION

NOTE: Installation of the GSK-3 secondary safety switch is recommended for LP and Natural gas fired appliances with a draft hood. This switch will detect exhaust gas spillage out of the draft hood due to a blocked vent system and/or inadequate draft during operation. When this switch senses spillage it interrupts the power supply to the gas valve which terminates the burner operation.

1.

Mount the GSK-3 on the lower edge of the draft hood with the exposed

 

 

thermal disk directed into the draft hood (See Figure 7)

 

2.

Route the electrical wires along the heating appliance cabinet within an

 

 

accepted wiring enclosure in accordance with the National Electrical

 

 

Code and any applicable local codes. Keep the wires away from any

 

 

HOT surfaces.

 

3.

Wire the switch into the low voltage thermostat circuit. Refer to the

Figure 7

 

appropriate wiring diagram in this manual.

 

 

4.

After installation, check the amperage through the thermostat circuit and adjust the anticipator if necessary.

 

CAUTION: The GSK-3 is a manual reset switch. Investigate the system thoroughly for the cause of any shut down and correct the problem before resetting the GSK-3 and restarting the system.

Diagram B – Internal Wiring Schematic for PVU-300