GENERAL WIRING INSTRUCTIONS
CAUTION: Disconnect electrical power before wiring power venter!
Connect line voltage (110/120 VAC) through junction box access hole labeled "120 VAC Only". Connect low voltage control wiring through junction box access hole labeled "24 VAC Control Wiring Only". VENTER MUST BE GROUNDED! Check ground circuit to make certain that venter has been properly grounded. The wiring must be protected by an over current protection circuit such as a fuse or circuit breaker rated at 15 amperes. Prevent wiring contact with any heat source.
IMPORTANT: The
NOTE: Wire the venter in accordance with the National Electrical Code and applicable local codes. Refer to Diagrams C and D for proper wiring specifications for a 24VAC Gas or 120VAC Oil fired appliance.
Diagram C – Wiring with 24 VAC Gas Valve
Diagram D – Wiring with a 120 VAC Oil Fired Primary Control