FieldServer FS-8700-20 Server Side Connection Descriptions, Server Side Node Descriptors

Models: FS-8700-20

1 22
Download 22 pages 19.12 Kb
Page 14
Image 14
5.3.Server Side Connection Descriptions

FS-8700-20 Profibus DP Driver Manual

Page 14 of 22

5.3.Server Side Connection Descriptions

The adapter used for the Profibus driver must be declared in the connections section.

Section Title

 

 

 

 

 

Connections

 

 

 

 

 

Column Title

Function

 

Legal Values

 

Adapter

Adapter Name

 

Prof_DP

 

Protocol

Specify protocol used

 

Profibus_DP

 

 

 

 

 

9600, 19200, 93.75K, 187.5K,

 

Profibus_DP_Baud

Specifies network baudrate

 

500K, 750K, 1.5M, 3M, 6M,

 

 

 

 

 

12M

 

Example

 

 

 

 

 

 

 

 

 

 

// Client Side Connections

 

 

 

 

Connections

 

 

 

 

 

Adapter,

 

Protocol,

Profibus_DP_Baud

 

Prof_DP,

 

Profibus_DP,

19200

 

5.4.Server Side Node Descriptors

 

Section Title

 

 

 

 

 

 

 

Nodes

 

 

 

 

 

 

 

 

 

 

 

 

 

Column Title

Function

 

Legal Values

 

 

Node_Name

Provide name for node

 

Up

to

32

alphanumeric

 

 

characters

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0-125

 

 

 

 

Node_ID

Station ID of the Slave

 

Must be same as Value used for

 

 

 

 

System_Station_Address

 

Protocol

Specify protocol used

 

Profibus_DP

 

 

 

 

 

 

 

 

 

 

Adapter

Specify which adapter

is

Prof_DP

 

 

 

 

connected to the FieldServer

 

 

 

 

 

 

Example

 

 

 

 

 

 

//Client Side Nodes

Nodes

 

 

 

Node_Name,

Node_ID,

Protocol,

Adapter

PDP_01,

1,

Profibus_DP,

Prof_DP

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com

Page 14
Image 14
FieldServer FS-8700-20 instruction manual Server Side Connection Descriptions, Server Side Node Descriptors