FS-8700-59 Canatal Sachnet

Driver Manual

5.4Server Side Map Descriptors

5.4.1FieldServer Specific Map Descriptor Parameters

Column Title

Function

Legal Values

Map_Descriptor_Name

Name of this Map Descriptor

Up to 32 alphanumeric characters

Data_Array_Na me

Name of Data Array where data is to be stored

One of the Data Array names from

 

in the FieldServer

“Data Array” section above

Data_Array_Location

Starting location in Data Array

0 to maximum specified in “Data Array”

 

 

section above

Function

Function of Server Map Descriptor

PASSIVE

5.4.2 Driver Specific Map Descriptor Parameters

 

Column Title

 

Function

 

Legal Values

Node_Name

 

Name of Node to fetch data from

 

One of the node names specified in

 

 

 

 

“Client Node Descriptor” above

Length

 

Length of Map Descriptor

 

1 - 1000 ( Maximum value is dependent

 

 

 

 

on the values of Cana_Series and

 

 

 

 

Cana_table. For more information see

 

 

 

 

section 6.1

Address

 

This term is used to refer to the offset into the

 

0,1,2,3 ...

 

 

 

 

 

 

Canatal device data table.

 

 

 

 

Each table first element is addressed as zero, the

 

 

 

 

2nd element as 1 etc.

 

 

 

 

The address & length must not exceed the

 

 

 

 

maximum length of he table being addressed.

 

 

 

 

 

 

 

Protocol Specific

 

 

 

 

Parameters

 

 

 

 

Cana_Series

 

Refers to the Canatal Corporation Inc. device

 

2,4,5,6,9

 

 

series number. Although different series of

 

 

 

 

equipment have similar tables with similar

 

 

 

 

contents they are not all the same, the contents

 

 

 

 

may vary and the data formats do vary.

 

 

Cana_Table

 

This is the data table in the device you wish to

 

Non zero integers. Legal values may be

 

 

read.

 

obtained by reading section 6.1.

Length

 

Length of Map Descriptor

 

1 - 1000 ( Maximum value is dependent

 

 

 

 

on the values of Cana_Series and

 

 

 

 

Cana_table. For more information see

 

 

 

 

section 6.1

Cana_Format *

 

Used to over-ride the default data storage method

 

Bype, BCD, BCD4, Float, Word,

 

 

the driver assigns to the table. This paramater

 

Percent, Swap_int.

 

 

may be required when reading data from a table

 

 

 

 

with midex data formats. See section 6.1 to

 

 

 

 

identify which table have mixed data formats and

 

 

 

 

what the default type the driver allocates to the

 

 

 

 

table.

 

 

5.4.3 Timing Parameters

Column Title

Function

Legal Values

Scada_Hold_Timeout

Specifies time server side waits before responding to client

>1.0s

 

that node is offline on FieldServer client side.

 

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 (408) 262-2299 fax: (408) 262-9042

Visit our website: www.fieldserver.com E-mail: support@fieldserver.com

Page 10

Page 12
Image 12
FieldServer FS-8700-59 instruction manual Server Side Map Descriptors, FieldServer Specific Map Descriptor Parameters

FS-8700-59 specifications

The FieldServer FS-8700-59 is a versatile communication gateway designed to facilitate seamless integration between various building automation systems and electronic devices. This robust device is part of the FieldServer family, known for its commitment to enabling interoperability in heterogeneous environments. The FS-8700-59 caters primarily to system integrators, facility managers, and operators seeking to streamline their operations and enhance the efficiency of their systems.

One of the main features of the FS-8700-59 is its extensive protocol support. This gateway is capable of translating between over 130 different protocols, making it a vital tool for managing diverse communication needs across disparate systems. This includes compatibility with popular protocols such as Modbus, BACnet, LonWorks, and many others. As a result, the FS-8700-59 ensures that various devices can communicate effectively, regardless of their original communication format.

The FS-8700-59 is equipped with a powerful processing engine, which enhances its performance and enables real-time data processing. This capability allows the gateway to handle large volumes of data efficiently, ensuring that system integrators can rely on timely communication between devices. Additionally, it features configurable data logging capabilities that help users gather and analyze valuable insights about system performance.

Another significant characteristic of the FS-8700-59 is its user-friendly interface. The device comes with built-in web server technology, allowing users to configure and manage the system easily via a standard web browser. This eliminates the need for specialized software, making it accessible for technicians with varying levels of expertise. Configuration wizards guide users through the setup process, simplifying the deployment of new systems.

Security is also a priority for the FS-8700-59. It incorporates various security protocols to safeguard data transmission, ensuring that sensitive information remains protected from unauthorized access. This feature is increasingly critical as organizations become more reliant on interconnected systems and cloud-based solutions.

The FS-8700-59 is designed for durability and longevity in demanding environments. Its robust casing protects it from dust, moisture, and other environmental factors, making it suitable for a wide range of applications. Overall, the FieldServer FS-8700-59 stands out as a reliable, powerful, and user-friendly solution for integrating diverse building automation systems, making it an indispensable tool for modern facility management.