FS-8700-59 Canatal Sachnet

Driver Manual

The Data formats are used internally in the driver but they do indicate to the user the type of data array that should be used for storage in the FieldServer.

Data Type

Suitable Data Array Types

CANA_BCD_CODED

BYTE,UINT16,UINT32,FLOAT

CANA_BYTE

BYTE,UINT16,UINT32,FLOAT

CANA_SWAP_INT

SINT16, SINT32, UINT16,UINT32,FLOAT

CANA_BCD_4

BYTE

CANA_WORD

UINT16,UINT32,FLOAT

CANA_FLOAT

FLOAT

6.2 Troubleshooting

The following messages are produced by the driver. Those marked FYI are for the user's information only and do not require any corrective action. Those marked Error require some action from the user.

CANA:#1

FYI. Station illegal -Forcing from %d to 59

 

Valid station numbers are 1-63.

CANA:#2

Error. Series & table numbers are rqd. Correct MapDesc=<%s>

 

The series and table parameters cana_series and cana_table must be specified in

 

the map descriptors.

CANA:#3

Error. Illegal Series Number. Correct MapDesc=<%s>

 

The series number specified cannot be processed by this driver. Read the vendor

 

documentation and correct the CSV file.

CANA:#4

Error. Illegal Table Number(%d). Correct MapDesc=<%s>

 

All Canatal equipment series do not have the same number of tables. Read the

 

vendor documentation and correct the CSV file.

CANA: #5

Error. Series & table numbers are rqd. Empty Table. Correct MapDesc=<%s>

 

The series & table combination specified are not valid. Read the vendor

 

documentation and correct the CSV file.

CANA:#6

Error. Start address is beyond end of table. MapDesc=<%s>

 

The address is the equivalent term to offset in the Vendor literature. Different

 

tables have different lengths. The lengths may also be different based on the

 

series number of the equipment. Read the vendor documentation and correct the

 

CSV file.

CANA:#7

FYI. Requested too many elements from table. MapDesc=<%s>

 

Changed request from %u to %u

 

The driver has truncated you data_length so that it does not read/write beyond the

 

end of a table.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 (408) 262-2299 fax: (408) 262-9042

Visit our website: www.fieldserver.com E-mail: support@fieldserver.com

Page 14

Page 16
Image 16
FieldServer FS-8700-59 instruction manual Troubleshooting

FS-8700-59 specifications

The FieldServer FS-8700-59 is a versatile communication gateway designed to facilitate seamless integration between various building automation systems and electronic devices. This robust device is part of the FieldServer family, known for its commitment to enabling interoperability in heterogeneous environments. The FS-8700-59 caters primarily to system integrators, facility managers, and operators seeking to streamline their operations and enhance the efficiency of their systems.

One of the main features of the FS-8700-59 is its extensive protocol support. This gateway is capable of translating between over 130 different protocols, making it a vital tool for managing diverse communication needs across disparate systems. This includes compatibility with popular protocols such as Modbus, BACnet, LonWorks, and many others. As a result, the FS-8700-59 ensures that various devices can communicate effectively, regardless of their original communication format.

The FS-8700-59 is equipped with a powerful processing engine, which enhances its performance and enables real-time data processing. This capability allows the gateway to handle large volumes of data efficiently, ensuring that system integrators can rely on timely communication between devices. Additionally, it features configurable data logging capabilities that help users gather and analyze valuable insights about system performance.

Another significant characteristic of the FS-8700-59 is its user-friendly interface. The device comes with built-in web server technology, allowing users to configure and manage the system easily via a standard web browser. This eliminates the need for specialized software, making it accessible for technicians with varying levels of expertise. Configuration wizards guide users through the setup process, simplifying the deployment of new systems.

Security is also a priority for the FS-8700-59. It incorporates various security protocols to safeguard data transmission, ensuring that sensitive information remains protected from unauthorized access. This feature is increasingly critical as organizations become more reliant on interconnected systems and cloud-based solutions.

The FS-8700-59 is designed for durability and longevity in demanding environments. Its robust casing protects it from dust, moisture, and other environmental factors, making it suitable for a wide range of applications. Overall, the FieldServer FS-8700-59 stands out as a reliable, powerful, and user-friendly solution for integrating diverse building automation systems, making it an indispensable tool for modern facility management.