5.2.Server Side Connection Descriptors
| Section Title |
|
|
|
|
|
|
|
| |
| Connections |
|
|
|
|
|
|
|
| |
| Column Title |
|
| Function |
|
|
| Legal Values |
| |
| Port |
|
| Specify which port the device is connected to | the |
|
| |||
|
|
|
| FieldServer |
|
|
|
|
| |
| Baud |
|
| Specify baud rate |
|
| 9600, 38400, 7680012 |
| ||
| Parity* |
|
| Specify parity |
|
|
| None, Odd, Even |
| |
| Data_Bits* |
| Specify data bits |
|
| 7, 8 |
| |||
| Stop_Bits* |
| Specify stop bits |
|
| 1, 2 |
| |||
| Protocol |
| Specify protocol used |
|
| BACnet_MSTP |
| |||
| Connection_Type |
| Specify if the connection must be in Master_Mode or |
| MSTP_Master_Mode |
| ||||
|
| in Slave_Mode |
|
|
| MSTP_Slave_Mode |
| |||
|
|
|
|
|
|
|
| |||
|
|
|
| Specify the highest possible MAC_Address that exists |
|
|
| |||
| Max_Master* |
| on the | MSTP network. | Only applicable | for |
| |||
|
|
|
| MSTP_Master Mode connections. (See also section |
|
|
| |||
|
|
| 4.7)13 |
|
|
|
|
|
| |
|
|
|
| Specify the maximum number of information frames |
|
|
| |||
| Max_Info_Frames* |
| the connection may send before it must pass | the |
| |||||
|
|
|
| token. Only applicable for MSTP_Master Mode |
|
|
| |||
|
|
|
| connections. 13 |
|
|
|
|
| |
| Example |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
| ||
// | Server Side Connections |
|
|
|
|
| ||||
| Connections |
|
|
|
|
|
|
|
| |
| Port, | Baud, |
| Parity, | Data_Bits, | Stop_Bits, | Protocol, |
| ||
| R1, | 38400, |
| None, | 8, | 1, | BACnet_MSTP, |
|
5.3.Server Side Node Descriptors14
Section Title |
|
|
Nodes |
|
|
Column Title | Function | Legal Values |
Node_Name | Provide name for node | Up to 32 alphanumeric |
characters15 | ||
Node_ID | Node ID | 1 - 4194303 |
Protocol | Specify protocol used | BACnet_MSTP |
10P1 to P8 will require the optional
11Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware.
1276800 baud is supported on the X30, X25 and ProtoCessor
13For server configurations the Max_Master and Max_Info_Frames parameters (or properties) can be overridden from a BACnet Client by using the “Write Property” command. Note that when the FieldServer is restarted, the default values as specified in the configuration file will be applied
14Only one Server Nodes may be defined for each connection. For information on support for multiple virtual server nodes on a single connection please contact the Sales Department."
15For HMI systems, this name will appear as the object name
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408)