4.4.Client Side Node Descriptors

FS-8700-73 BACnet MSTP Driver Manual

Page 9 of 24

 

 

4.4.Client Side Node Descriptors

 

Section Title

 

 

 

 

 

 

 

 

Nodes

 

 

 

 

 

 

 

 

Column Title

 

Function

 

Legal Values

 

 

Node_Name

Provide name for node

 

Up to 32 alphanumeric

 

 

 

characters

 

 

 

 

 

 

 

 

 

 

Node_ID

Specify the BACnet Device object instance. 6

1 - 4194303

 

 

 

Protocol

Specify protocol used

 

BACnet_MSTP

 

 

 

Port

Specify port

 

 

P1-P87, R1-R28

 

 

 

 

 

 

 

1-127 (for Master

 

 

MAC_Address

MAC_Address of the physical server node.6

 

Nodes)

(for

Slave

 

 

 

 

 

1-254

 

 

 

 

 

 

Nodes)

 

 

 

 

 

Use this parameter if the remote MSTP server device

 

1,2,3.... 16 bit positive

 

 

Network_Number*

is on another BACnet network connected via a router.

 

numbers.

 

 

 

 

 

 

 

5

 

 

 

 

Example

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

// Client Side Nodes

 

 

 

 

 

 

 

Nodes

 

 

 

 

 

 

 

 

Node_Name,

Node_ID,

Protocol,

 

Port

 

 

 

 

BCU_1,

1,

BACnet_MSTP,

 

R1

 

 

 

6Either Node_ID OR MAC_Adddress must be specified. If the Server Node supports Who-Is and I-Am

then it is better to use the Node_ID parameter.

7 P1 to P8 will require the optional RS-485 converter (Part # 4301-00)

8 Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Tel: (408) 262-2299 Fax: (408) 262-9042 Toll Free: (888) 509-1970 email: support@fieldserver.com