FieldServer FS-8700-73 Server Side Map Descriptors, Driver Specific Map Descriptor Parameters

Models: FS-8700-73

1 24
Download 24 pages 23.23 Kb
Page 15
Image 15
5.4.Server Side Map Descriptors

FS-8700-73 BACnet MSTP Driver Manual

Page 15 of 24

 

 

5.4.Server Side Map Descriptors

5.4.1.FieldServer Specific Map Descriptor Parameters

Column Title

Function

Legal Values

Map_Descriptor_Name

Name of this Map Descriptor

Up to 32 alphanumeric characters.

 

Name of Data Array where

One of the Data Array names from

Data_Array_Name

data is to be stored in the

“Data Array” section

 

FieldServer

 

Data_Array_Offset

Starting location in Data Array

0 to Data_Array_Length-1 as

specified in “Data_Array” section

 

 

Function

Function of Server Map

Server

 

Descriptor

 

5.4.2.Driver Specific Map Descriptor Parameters

 

Column Title

 

 

Function

 

 

Legal Values

 

 

 

 

 

 

 

 

 

 

One of the node names

 

Node_Name

Name of FieldServer Node

 

specified in “Server Node

 

 

 

 

 

 

 

 

 

Descriptor” above

 

Data_Type

 

Data type in BCU

 

 

AI, AO, AV, BI, BV, MI, MO,

 

 

 

 

 

MV17

 

Object_Instance

 

Address of the object

 

 

0, 1, 2, 3, …

 

 

 

 

 

 

 

 

Units

 

The object units

 

 

Appendix 1

 

 

 

 

 

 

Data_Array_Low_Scale*

Scaling zero in Data Array

 

-32767 to 32767, 0

 

 

 

 

 

 

Data_Array_High_Scale*

Scaling max in Data Array

 

-32767 to 32767, 100

 

 

 

 

 

 

 

 

 

 

Node_Low_Scale*

 

Scaling

zero

in

Connected

 

-32767 to 32767, 0

 

 

 

Node

 

 

 

 

 

 

 

 

Node_High_Scale*

 

Scaling

max

in

Connected

 

-32767 to 32767, 100

 

 

 

Node

 

 

 

 

 

 

 

Active_Text

 

Specify

the

Active

Text

 

Any legal BACnet ASCII string

 

property of the Object 18

 

 

 

 

 

Specify

the

Inactive

Text

 

 

 

 

Inactive_Text

 

property of the Object (See

Any legal BACnet ASCII string

 

 

 

note12)

 

 

 

 

 

 

 

 

 

 

Specify

 

the

 

startup

 

 

 

 

Relinquish_Default

 

Relinquish_Default

Property

Any legal BACnet ASCII string

 

 

 

value for this Object (See

 

 

 

 

 

 

note12)

 

 

 

 

 

 

 

 

 

 

This

over-writes

the

 

 

 

 

Custom_Type

 

Data_Type with a numerical

1..1023

 

 

 

value for the Data_Type. e.g.

 

 

 

 

Analog Value = 2

 

 

 

 

 

 

 

 

This over-writes the Property

 

 

 

 

Custom_Prop

 

with a numerical value for the

1..4194303

 

 

 

 

property. e.g. Present Value =

 

 

 

 

 

85

 

 

 

 

 

 

 

17Refer to Appendix A.1 for further information.

18See the BACnet DFS to determine if a particular object supports this property

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Tel: (408) 262-2299 Fax: (408) 262-9042 Toll Free: (888) 509-1970 email: support@fieldserver.com

Page 15
Image 15
FieldServer FS-8700-73 instruction manual Server Side Map Descriptors, FieldServer Specific Map Descriptor Parameters