4.Configuring the FieldServer as a BACnet MSTP Client

FS-8700-73 BACnet MSTP Driver Manual

Page 7 of 24

 

 

4.Configuring the FieldServer as a BACnet MSTP Client

For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” sample files provided with the FieldServer).

This section documents and describes the parameters necessary for configuring the FieldServer to communicate with a BACnet MSTP Server.

4.1.Data Arrays/Descriptors

The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for BACnet MSTP communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays” section, the destination device addresses need to be declared in the “Client Side Nodes” section, and the data required from the servers needs to be mapped in the “Client Side Map Descriptors” section. Details on how to do this can be found below.

Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.

 

Section Title

 

 

 

 

Data_Arrays

 

 

 

 

Column Title

Function

 

Legal Values

 

Data_Array_Name

Provide name for Data Array

 

Up to 15 alphanumeric

 

 

characters

 

 

 

 

 

 

 

 

Float, Bit, Uint16, Uint32,

 

Data_Format

Provides data format

 

Sint16, Sint32, Packed_Bit,

 

 

Byte, Packed_Byte,

 

 

 

 

 

 

 

 

Swapped_Byte

 

Data_Array_Length

Number of Data Objects

 

1-10,000

 

 

 

 

 

 

Example

 

 

 

 

 

 

 

 

 

// Data Arrays

 

 

 

 

Data_Arrays

 

 

 

 

Data_Array_Name,

Data_Array_Format,

Data_Array_Length

 

DA_AI_01,

Float,

200

 

DA_AO_01,

Float,

200

 

DA_DI_01,

Bit,

200

 

DA_DO_01,

Bit,

200

4.2.Setting the FieldServer Node_ID

Section Title

 

 

FieldServer

 

 

Column Title

Function

Legal Values

System_Node_ID

Specify the MAC_Address of the

1-254

 

FieldServer. (See Appendix C.1)

 

Example

 

 

// FieldServer

 

 

FieldServer

 

 

Title,

System_Node_ID

 

BACnet_MSTP,

11

 