FS-8700-86 Carrier DataPort

Page 10 of 32

5.Configuring the FieldServer as a Carrier DataPort Server

For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” sample files provided with the FieldServer).

This section documents and describes the parameters necessary for configuring the FieldServer to communicate with a Carrier DataPort Client.

The FieldServer can be configured to emulate a Carrier DataPort Device. The user is able to define a variable quantity of variables. The FieldServer may be polled and will respond like a DataPort device.

The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for Carrier DataPort communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays” section, the FieldServer virtual node(s) needs to be declared in the “Server Side Nodes” section, and the data to be provided to the Clients needs to be mapped in the “Server Side Map Descriptors” section. Details on how to do this can be found below.

Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.

5.1.Data Arrays

 

Section Title

 

 

 

 

 

 

 

Data_Arrays

 

 

 

 

 

 

 

Column Title

Function

 

 

Legal Values

 

 

Data_Array_Name

Provide name for Data Array

Up

to

15

alphanumeric

 

 

characters

 

 

 

 

 

 

 

 

 

Provide data format. Each Data Array can

Float,

 

Bit,

Uint16, Sint16,

 

 

Data_Format

Packed_Bit, Byte, Packed_Byte,

 

 

 

only take on one format.

Swapped_Byte

 

 

 

 

 

 

 

 

 

Number of Data Objects. Must be larger

 

 

 

 

 

 

Data_Array_Length

than the data storage area required for

1-10,000

 

 

 

 

 

the data being placed in this array.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Example

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

// Data Arrays

 

 

 

 

 

 

 

//

 

 

 

 

 

 

 

Data_Arrays

 

 

 

 

 

 

 

Data_Array_Name,

Data_Format,

Data_Array_Length

 

 

DA_AI_01,

Uint16,

200

 

 

 

 

 

DA_AO_01,

Uint16,

200

 

 

 

 

 

DA_DI_01,

Bit,

200

 

 

 

 

 

DA_DO_01,

Bit,

200

 

 

 

 

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com

Page 10
Image 10