Error Message

 

Explanation

 

 

 

 

 

 

There DataPort device responded but the response reports an error. The

 

 

 

 

 

error number is printed in the message. The message also reports the

 

 

 

 

 

name of the node that was polled.

 

 

 

 

 

 

The following 6 errors are documented. For other errors contact the

 

 

 

 

 

Carrier Vendor.

 

 

 

 

 

 

#1 Invalid Command : The digit 1 returned as an error code means that

 

 

 

 

 

the last ASCII character sent to the DATAPORT by the off-network

 

 

 

 

 

device is not one that the DATAPORT recognizes as a command.

 

 

 

 

 

#2 No Display Table : The digit 2 returned as an error code means that

 

 

 

 

 

the off-network device has commanded the DATAPORT to transmit data

 

 

 

 

 

from a controller that is properly configured in the DATAPORT, but the

 

 

 

 

 

controller does not contain a point display table.

 

 

 

 

 

 

#3 CCN Bus Communication Error: The digit 3 returned as an error code

 

 

 

 

 

means that the DATAPORT cannot transmit data from the requested

 

 

CarrDP:#33

Err.

DataPort

controller because a communication error occurred while the

 

 

DATAPORT was acquiring data from that controller.

 

 

 

responded

with

Err=%d.

 

 

 

 

Device=%s

 

 

#4 Database Full : The digit 4 returned as an error code means that the

 

 

 

 

 

 

 

 

 

 

off-network device has commanded the DATAPORT to transmit data

 

 

 

 

 

from a controller that is properly configured in the DATAPORT, but the

 

 

 

 

 

controller is beyond the 900 point limit. For example, if controllers 1

 

 

 

 

 

through 10 each contain 90 points, a command for the DATAPORT to

 

 

 

 

 

transmit data from controller 11, 12, 13, 14, or 15 will result in error code

 

 

 

 

 

4.

 

 

 

 

 

 

#5 DATAPORT Busy : The digit 5 returned as an error code means that

 

 

 

 

 

a static data update is in progress, preventing the DATAPORT from

 

 

 

 

 

responding successfully to a Send Controller Data Command or a Send

 

 

 

 

 

Data Periodically command.

 

 

 

 

 

 

#6 Controller Not Configured : The digit 6 returned as an error code

 

 

 

 

 

means that the off-network device has commanded the DATAPORT to

 

 

 

 

 

transmit data from a controller that is not configured in the DATAPORT.

 

 

 

 

 

For example, if only controllers 1 through 5 are configured in the

 

 

 

 

 

DATAPORT, a command of 0 (Send Controller Data for Controller 15)

 

 

 

 

 

will result in error code 6.

 

 

 

 

 

 

 

CarrDP:#99 Err. Cant open

This message should only be printed in simulation mode (QA testing). If

 

 

INI file for response.

you see this message call Tech Support.

 

 