FS-8700-86 Carrier DataPort

Page 11 of 32

5.2.Server Side Connections

 

Section Title

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Connections

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Column Title

 

 

 

 

 

Function

 

 

 

 

 

Legal Values

 

 

Port

 

 

Specify which port the device is connected to

P1-P8, ( R1-R2 with converter)4

 

 

 

 

 

the FieldServer

 

 

 

 

 

 

 

 

 

 

 

 

Baud*

 

 

Specify baud rate

 

 

 

 

300,

600 ,

1200,

2400, 9600

 

 

 

 

 

 

 

 

 

(Vendor limitation)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parity*

 

 

Specify parity

 

 

 

 

 

 

None (Vendor limitation)

 

 

Data_Bits*

 

 

Specify data bits

 

 

 

 

 

8 (Vendor limitation)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Stop_Bits*

 

 

Specify stop bits

 

 

 

 

 

1 (Vendor limitation)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Protocol

 

 

Specify protocol used

 

 

 

CarrierDP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Handshaking*

 

 

Specify hardware handshaking

 

 

 

None

 

 

 

 

 

Example

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

// Server Side Connections

 

 

 

 

 

 

 

 

 

 

 

 

Connections

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Port,

Baud,

Parity,

Data_Bits,

Stop_Bits,

Protocol ,

Handshaking,

Poll_Delay

 

 

P8,

9600,

None,

8

,

1

,

CarrierDP,

None

,

0.100s

 

5.3.Server Side Node Descriptors

 

Section Title

 

 

 

 

 

Nodes

 

 

 

 

 

Column Title

Function

 

Legal Values

 

 

Node_Name

Provide name for Node

 

Up to 32 alphanumeric

 

 

 

characters

 

 

 

 

 

 

 

 

DataPort station address of physical Server Node.

 

 

 

 

These correspond to the ‘devices’ configured in the

 

 

 

 

DTPConfig. Thus the Node_ID is not the address of

 

 

 

Node_ID

the final CCN device.

 

1-15

 

 

 

The DataPort DTPConfig table maps a device

 

 

 

 

number (1...15) to a bus number (0-239). Use the

 

 

 

 

Node_ID to tell the driver which device to use.

 

 

 

Protocol

Specify protocol used

 

CarrierDP

 

 

Example

 

 

 

 

 

 

 

 

 

 

 

// Server Side Nodes

 

 

 

 

Nodes

 

 

 

 

 

Node_Name,

Node_ID,

Protocol ,

Port5

 

 

FAN1 ,

1 ,

CarrierDP,

P8

 

4Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction

manual for details of the ports available on specific hardware.

5 It is common to leave server nodes unconnected to a port. This means that the FieldServer can respond with the Node’s data irrespective of which port the request is received on.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com

Page 11
Image 11
FieldServer instruction manual FS-8700-86 Carrier DataPort Server Side Connections, Server Side Node Descriptors