FS-8700-86 Carrier DataPort

Page 13 of 32

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Column Title

 

 

Function

Legal Values

 

 

 

 

If this parameter is defined then its value must be

 

 

 

 

 

 

 

 

 

 

the name of a Data Array. Instead of the driver

The name of Data Array

 

 

 

DA_Byte_Name*

returning a static Field Status, it will extract the

defined in

 

 

the

Data

 

 

 

 

value located at the given offset and use this

Arrays section.

 

 

 

 

 

 

value as the Field Status.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

If the variable has a discrete state, use this

 

 

 

 

 

 

 

 

 

 

parameter to define the word that describes the

 

 

 

 

 

 

 

 

 

 

state when the variable’s value is 1.

 

 

 

 

 

 

 

 

 

 

OR

 

NUMERIC

 

 

 

 

 

 

 

 

 

Use one of the keywords to tell the driver to send

 

 

 

 

 

 

 

 

 

TIME

 

 

 

 

 

 

 

 

 

the value of the associated array elements:

STRING

 

 

 

 

 

 

 

 

 

NUMERIC – a number

 

 

 

 

 

 

 

 

On_String

DOW

 

 

 

 

 

 

 

 

TIME - a time value formatted as hh:mm

 

 

 

 

 

 

 

 

 

Or any other Ascii string

 

 

 

 

STRING - a string of bytes

 

 

 

 

which may

not

contain

 

 

 

 

DOW – occupancy string

 

 

 

 

spaces.

 

 

 

 

 

 

 

 

 

When using the string keyword the driver reads x

 

 

 

 

 

 

 

 

 

consecutive array elements and treats them as

 

 

 

 

 

 

 

 

 

 

ASCII character values in forming the response.

 

 

 

 

 

 

 

 

 

 

X is defined by the length parameter.

 

 

 

 

 

 

 

 

 

 

If the variable has a discrete state, use this

 

 

 

 

 

 

 

 

 

Off_String

parameter to define the word that describes the

An ASCII

string

which

 

 

 

state when the variable’s value is zero. If you

may not contain spaces.

 

 

 

 

have used a keywords described above then

 

 

 

 

 

 

 

 

 

 

simply put a dash in this field.

 

 

 

 

 

 

 

 

 

Length

Always set the length to 1 unless you use the key

1

 

 

 

 

 

 

 

 

 

word ‘STRING’ as the On_String parameter.

 

 

 

 

 

 

 

5.4.3.

Timing Parameters

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Column Title

 

 

Function

 

 

 

Legal

 

 

 

 

 

 

 

 

 

Values

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Scada_Hold_Timeout

 

Specifies time Server side waits before responding to Client

 

 

>1.0s

 

 

 

 

that node is offline on FieldServer Client side.

 

 

 

 

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com

Page 13
Image 13
FieldServer instruction manual FS-8700-86 Carrier DataPort, Numeric, Time, String, Dow