Page 4 of 6

FS-8704-11 Telnet Driver Manual

Page 4 of 6

4.Using the Serial Port Capture

4.1.Manual Serial Port Capture

Once the FieldServer is up and running, connect to it using its IP address.

Type port <Enter>

When prompted, enter the name of the port to be captured (e.g. P8 <Enter>). The driver will check if the desired port has been initialized by a “port” statement in the configuration file. If the port has been initialized and is available, the driver will wait for any current polls to finish, and will then print “Connected” to indicate that the port is now under the control of the Telnet client. If a device is connected to the captured serial port, you can now communicate with it as if you had a direct serial connection.

To disconnect the port from the Telnet session, press Ctrl-C.This will also work while the driver is still waiting for an active poll to complete.

To terminate the Telnet session, close the Telnet client.

Notes:

1.If a port has been manually captured in one Telnet session, it will not be available to any other Telnet sessions. Other sessions attempting to capture the port will be returned to the command prompt with an error message. To release a port, the connected Telnet session must be disconnected.

2.Capturing a port makes the port unavailable to any protocol driver on the FieldServer that might have been communicating with the device. Refer to the comments on session_timeout above on how to prevent an indefinite lockout if a Telnet session with a port capture is forgotten on.

3.A Serial connection needs to be specified before defining the Telnet connection (which has autoconnect_port) or else the FieldServer will give system error.

Example

Not Correct:

Connections

Adapter,

Protocol,

Autoconnect_port

 

N1,

TLN,

P1

 

 

 

 

 

 

 

Correct:

 

 

 

 

Connections

 

 

 

 

Adapter,

Baud,

Timeout,

Protocol

 

P1,

9600,

10s,

-

 

Connections

 

 

 

 

Adapter,

Protocol,

Autoconnect_port

 

N1,

TLN,

P1

 

 

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com

Page 6
Image 6
FieldServer FS-8704-11 instruction manual Using the Serial Port Capture, Page 4 of, Manual Serial Port Capture, Example