Installation (for qualified installers only)

2 3

Horizontal Terminations using 8” Diameter Vent

The termination must fall within the shaded area shown in the chart. Use the indicated restrictor position.

20' (max)

15feet

10feet

5feet

0feet

0feet

5feet

10feet

15feet

20feet

25'(max)

Restrictor

Position #7

NOTE:

Restrictor positions are based upon lab tests. The ideal restrictor position may vary slightly.

Restrictor

Position #1

6-5/8" to 8" dia. Adapter

(must be placed directly off the top of the fireplace - Part # 925T)

0feet

5feet

10feet

15feet

20feet

25'(max)

20' (max)

15feet

10feet

5feet

0 feet

H2H1

NOTE:

Horizontal sections require a 1/4" rise every 12" of travel.

The maximum vertical height is 20'.

The maximum horizontal length is 25'.

One horizontal elbow (45° or 90°) is allowed when using 8" vent. The horizontal vent length is calculated by adding the length before and after the elbow (H1 + H2 = horizontal vent length).

Vertical

Elbow

Horizontal

Elbow