OR
If local codes DO NOT PERMIT connecting cabinet-grounding conductor to neutral (white) wire in junction box:
7 Separate the factory-crimped green and white oven cable wires.
8 Connect white oven cable wire to neutral (white) wire in junction box.
9 Connect the green grounding oven cable wire to a grounded wire in the junction box.
10 Replace the junction box cover.
OR
If connecting to a four-wire electrical system:
7 Separate green and white oven cable wires.
8 Connect white oven cable wire to neutral (white) wire in junction box.
9 Connect the green grounding oven cable wire to the (green) grounding wire in the junction box.
Do not connect green grounding wire to neutral (white) wire in junction box.
10 Replace the junction box cover.
Replace the junction box cover.
8
Installation instructions
6 Connect electrical connection according to local codes and ordinances.
If local codes PERMIT connecting cabinet- grounding conductor to neutral white wire in the junction box:
7 Connect the factory-crimped green and white oven cable wires to the
neutral (white) wire in the junction box.
US
junction box
red wires
white wire
white and green grounding oven wires - factory crimped
junction box
red wires
green grounding oven wires - factory crimped
cable from power supply
black wires
cable from power supply
white wires
black wires
9