2Page 2-6 Installation and Wiring
TS-TPI Installation and Wiring Guide

Stand AloneTS-TPI with Automatic Tank Gauge TS-1001 or

TS2001 and TPCs

Figure 2-5

Communication between ATG and TPCs, no additional ATG options required for full

operation

Stand Alone TS-TPI requires separate 120 - 240 vac, 50/60 hz, power

See Tank Sentinel Installation Guide for specific ATG instructions

TPCs that can be installed are MagVFC, IST-VFC, STP-SCI, STP-SC and STP-

SCIII. Available functions are limited on the IST-VFC, STP-SC and the STP-SCIII

controllers, see troubleshooting section for details

Connect TPCs so all Stand alone TPCs are on the same port and Master/Slave
configured units are on their own port. Address TPCs so controllers on same port
have unique addresses. If similar type stand alone TPCs are installed on the same
port as Master/Slave TPCs the stand alone TPCs will be seen as Slave units.
INPUTS
TS-LLD
485B
485A
S,RTN
DSY
IN 1
GND
IN 2
GND
TS1001 OR TS2001 ONLY

ATG

RED
BLACK
WHITE
BLACK
WHITE
RED

STAND ALONE TPI

TXD 485-
GND
RXD 485+
TXD 485-
GND
RXD 485+
TXD 485-
GND
RXD 485+
TXD 485-
GND
RXD 485+
TXD 485-
GND
RXD 485+
HOST PORT
PORT 1
PORT 2
PORT 3
PORT 4
ADDITIONAL TPC
GROUPS
RED
WHITE
BLACK
SEE TANK SENTINEL INSTALLATION GUID E
(PART # 000-1050), THIS TPI USER'S GUIDE
AND APPROPRIATE
TPC INSTALLATION AND OWNER'S MANUAL
FOR COMPLETE WIRING I NFORMATION
CABLE-BELDEN CONDUCTOR#9365-18AWG OR EQUIVALENT
+ G
RS485
TPC
CONTROLLERS MAY INCLUDE THE
MagVFC, STP-SCI, S TP -S C III, VF C
AND STP-SC
ADDITIONAL
TPC CONNECTIONS
RED
WHITE
BLACK
GND L2/N L1
INPUT POWER
120 -240 Vac 50/60 hz
TS-TPI
RESET
TPC FAULT
RESET
ALARM
SILENCE