GE EPM 5350 EPM 5300 Series Meters Electrical Installation, Connecting the Current Circuit, Feet

Models: EPM 5300 EPM 5200 EPM 5350

1 134
Download 134 pages 15.43 Kb
Page 17
Image 17

GE Consumer & Industrial

Multilin

EPM 5300 Series Meters

Chapter 3: Electrical

Installation

3.1Connecting the Current Circuit

Install the wiring for the current at 600V AC insulation as a minimum. The cable connector should be rated for 6 Amps or greater and have a cross-sectional area of 16 AWG minimum.

Mount the current transformers (CTs) as close as possible to the meter for best accuracy. The following table illustrates the maximum recommended distances for various CT sizes, assuming the connection is via 16 AWG cable.

Table 3–1:CT Size and Maximum Distance

 

 

CT Size

Maximum Distance (CT to Meter)

 

 

2.5 VA

10 Feet

 

 

5.0 VA

15 Feet

 

 

7.5 VA

30 Feet

 

 

10.0 VA

40 Feet

 

 

15.0 VA

60 Feet

 

 

30.0 VA

120 Feet

 

 

DO NOT leave secondary of the CT open when primary current is flowing. This causes high voltage that will overheat the secondary of the CT. Use a shorting block on the secondary of the CT.

EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL

3–5

Page 17
Image 17
GE EPM 5350, EPM 5200 EPM 5300 Series Meters Electrical Installation, Connecting the Current Circuit, Feet